49

Press button once briefly to deactivate
the line editing mode.

Press button once briefly to enter the
parameterisation window for the following
settings:

Proportional band X

p

Control hysteresis

24 h purging pulse for continuous
blowdown valve

Operating position of intermittent
blowdown valve

Relay contact 4 / automatic intermittent
boiler blowdown

Press button once briefly to enter the
line where the M

AX

conductivity limit of the

LRR 1-40 can be adjusted.

The M

AX

switchpoint of the LRR 1-40 can

be adjusted in the same way as the
conductivity setpoint.

Press button twice briefly to activate the line
editing mode.

In this line you can set the proportional band X

p

.

X

p

= 0: Two-position (on-off) control

X

p

> 0: Modulating control

Basic Settings

– continued –

Adjusting conductivity controller

– continued –

flashing

once briefly

once briefly

once briefly

twice briefly