Basic settings – Flowserve URB 1 User Manual
Page 49
49
Press button once briefly to deactivate
the line editing mode.
Press button once briefly to enter the
parameterisation window for the following
settings:
■
Proportional band X
p
■
Control hysteresis
■
24 h purging pulse for continuous
blowdown valve
■
Operating position of intermittent
blowdown valve
■
Relay contact 4 / automatic intermittent
boiler blowdown
Press button once briefly to enter the
line where the M
AX
conductivity limit of the
LRR 1-40 can be adjusted.
The M
AX
switchpoint of the LRR 1-40 can
be adjusted in the same way as the
conductivity setpoint.
Press button twice briefly to activate the line
editing mode.
In this line you can set the proportional band X
p
.
X
p
= 0: Two-position (on-off) control
X
p
> 0: Modulating control
Basic Settings
– continued –
Adjusting conductivity controller
– continued –
flashing
once briefly
once briefly
once briefly
twice briefly