The CAN bus communication of a
controller is disrupted.

Check that the controller and the level
or conductivity electrode have been
mounted as specified in the wiring
diagram.

In our example there is a disruption in
the CAN bus communication of the low-
water level electrode 2 type NRG 16-40.

System Malfunctions

– continued –

Fault Finding List

– continued –

The conductivity electrode is
defective.

The internal connecting cables of the
conductivity electrode are short
circuited or interrupted.

Replace conductivity electrode
LRG 16-40.

The CAN bus communication of a
controller is disrupted.

Check that the controller and the level
or conductivity electrode have been
mounted as specified in the wiring
diagram.

In our example there is a disruption in
the CAN bus communication of the
switching controller type NRS 1-40.

If faults occur that are not listed
above, please contact our subsidiary
or agency in your country.

5 times briefly

once briefly

once briefly