Basic settings – Flowserve URB 1 User Manual
Page 58
Advertising
58
Basic Settings
– continued –
Adjusting LIN (linear) temperature compensation
Press button once briefly to activate
the line editing mode.
The split-screen main window shows
which GESTRA bus devices can be
indicated:
■
High-level limiter NRS 1-41
■
Low-level limiter NRS 1-40
■
Level switch NRS 2-40
■
Level controller NRR 2-40
■
Conductivity controller LRR 1-40
Press button four times briefly to enter the
window where the following parameters can
be set:
■
Linear temperature compensation [% / °C]
■
Recording a temperature curve
■
Cell constant C of the conductivity
electrode
The factory set default setting is “TK:LIN”.
4 times briefly
once briefly