MDE-4793A CFN Series Site Controller III Start-up Manual for CFN III Versions 3.5 and above · November 2008
Page 67
PPC
DC Power Measurement and Adjustment
3
The acceptable voltage range is +5.0 to +5.1 VDC, but try to adjust it as close as possible to
+5.0 VDC.
Note: There is an access hole in the power supply bracket to facilitate adjustment without
disassembly.
Figure 10-4: FPR +5 VDC Measurement Point
PPC
There are no DC power adjustments in the PPC.