Detergent pump, Adjusting detergent pump output rate, Fig. 23b fig. 23a – Greenheck Waterwash (458292) User Manual

Page 26: Sequence of wash operations

Advertising
background image

26

April 2005

®

Pump

Setting

0

1

2

3

4

5

6

Oz./min.

0

1.35

2.7

4.05

5.4

6.75

8.1

6

1

2

3

4

5

0

DETERGENT PUMP:

For proper operation of the detergent pump and wash system, hot water pressure must be between 40 PSI
(min.) and 60 PSI (max.). The water temperature range is 140°F to 180°F.

Water pressure, water temperature, grease accumulation, wash cycle length, wash cycle frequency, and the
type and amount of detergent used can influence cleaning effectiveness. In very heavy cooking operations,
additional washes may be necessary. The wash time can also be increased to a maximum of 10 minutes; the
wash time is factory set at four minutes. Consult Fig. 23A to change the wash time. If this is not effective,
manual cleaning may be necessary (hand scrubbing, steam cleaning or pressure washing).

Adjusting Detergent Pump Output Rate

Adjustment of the detergent flow may be necessary. Pump must be

OFF.

Use the following formula to determine proper pump setting: (Adjust pump setting as needed for proper
cleaning.)

0.3 oz./min. x Hood Length = Pump Setting

The minimum pump setting is #2.

To calculate the number of washes a full detergent
tank will deliver for a specific application, use these
formulas:

1)

Pump setting (oz. per min.) x Wash Length (4.0 min. std.)
= Oz. per wash

2)

320 oz. Tank Capacity = Number of Washes per Tank
Oz. per Wash

1. Knob

2. Wing

Nut

5. Screw

Adjust the Detergent Injectors Output:

1) With the pump and detergent injector off

hold adjustment knob(1) and loosen
wing nut.

2) Turn adjustment knob until the pointer

(3) indicates the desired setting. Six is
the maximum; zero is the minimum.

3) While still holding adjustment knob,

tighten wing nut.

3. Pointer

4. Yolk

Record Original Pump Setting at Start-up for Future Reference

Pump Setting = __________________

Fig. 23B

Fig. 23A

L1

N

1.1

1.0

0.7

3L

*

0.6

0.5

0.4

2L

*

0.3

0.2

0.1

0.0

1L

L+

M

1.5

1.4

1.3

1.2

1.1

1.0

0.7

0.6

0.5

0.4

0.3

0.2

0.1

0.0

1M

PROGRAMMABLE

CONTROLLER

OUTPUTS

INPUTS

FA

N

S

MAIN

SEQ. 1

SEQ. 2

SEQ. 3

SEQ. 4

SEQ. 5

SUPPL

Y

PUMP

FIRE

FA

N

O

N

OFF / W

A

SH

FIRE

TIMER

+15 SEC. COLD

+30 SEC. DET

.

+9 MIN. DRIP

+9 MIN. DR

Y

SEQUENCE OF WASH OPERATIONS

1 MIN. DRY (FANS ON) (OPTIONAL 10 MIN.)

1 MIN. DRAIN DOWN (OPTIONAL 10 MIN.)

15 MIN. SEQUENCE DELAY (OPT. 0 TO 45 MIN.)

30 SEC. DETERGENT PURGE (OPTIONAL 1 MIN.)

4 MIN. WASH (OPTIONAL 0 TO 10 MIN.)

15 SEC. COLD WATER PURGE (OPTIONAL 30 SEC.)

2. WITH A SMALL SCREDRIVER

DO NOT FORCE SCREW PAST ITS STOPS.

AJDUST TO THE DESIRED SETTING.

0

10 MIN.

4 MIN.

7 MIN.

POTENTIOMETERS:

40 MIN.

0

20 MIN.

60 MIN.

WASH TIME

SEQ. DELAY

3. NEW SETTING WILL TAKE EFFECT

WHEN POWER IS REAPPLIED.

1. DISCONNECT POWER BEFORE SERVICING.

TERM. 0.4 - ADD 15 SECONDS TO COLD WATER PURGE
TERM. 0.5 - ADD 30 SECONDS TO DETERGENT PURGE

4. ADDING 120V JUMPERS WILL:

TERM. 0.6 - ADD 9 MINUTES TO DRAIN DOWN TIME
TERM. 0.7 - ADD 9 MINUTES TO FAN ON DRY TIME

5. RECONNECT POWER.

2M

CPU 224

AC/DC/RLY

STOP

RUN

TERM

SEQ.

DELAY

WASH

TIME

1

0

SIEMENS

SF

RUN

STOP

SIMATIC
S7-200

24V FROM OUTPUT 0.2
OR OTHER ALWAYS "HOT"
24V ELECTRICAL SOURCE

JUMPERS FOR ADDITIONAL TIME

OPTIONAL FIELD INSTALLED

Waterwash Timing Adjustment for PLCs:
(PU214 & CPU224)

Advertising
This manual is related to the following products: