Fire Mode (Optional):

The waterwash system also provides water spray for the exhaust plenum when the system is in fire mode. This is
in addition to the hood’s automatic fire suppression system. When the fire suppression system discharges, it
activates the waterwash system (without the detergent) and the optional continuous cold water mist to spray
water within the exhaust plenum and turns on the fan circuit. The system will shut off when the fire protection
system is reset. It can also be shut off manually by turning off the water flow in the waterwash control station.
Exhaust fan will be on, Supply fan off

Waterwash Hood

Junction Box -
Hood Lights

Exhaust Duct Collar

Drain Pipe

Waterwash
Control Station

Hot Water Supply
to Control Station

Optional
Cold Water Supply
to Control Station

Vacuum Breaker

Detergent Line

Hot Water/Detergent to Hood

Detergent Check Valve

Optional Continuous Cold
Water Mist Supply Line

Internal components of hood
and control station are factory
piped and wired. All external
piping and wiring is by others.

Fig. 1

115 VAC 20 AMP service

Fire Sup. System NC Switch

Fan Control Center

Opt. Solenoid Valve

for Seq. Wash

Wiring to:

The system shown includes
a vacuum breaker for
backflow prevention. Some
state plumbing codes
require a reduced pressure
backflow preventer. See
page 7 for detailed control
panel layouts of each type.

Typical Installation: