Fire mode sequence of operation, Fig. 24 – Greenheck Waterwash (458292) User Manual

Page 28

Advertising
background image

28

April 2005

®

Fire Mode

Sequence of Operation

START

END

Override

Return to Normal

Open All Waterwash Hand

Valves

Reset Hoods Automatic Fire

Suppression System

N.C. Contacts Close

Reset Hoods Automatic Fire

Suppression System

N.C. Contacts Close

Manually Shut-off Water

with Hand Valves

Water Flow Stops

Push Start Fan Button

Exhaust Fan, Supply Fan and Optional

Continuous Cold Water Mist will start

for the normal Cooking Operation.

Start Fan Light ON

Push Stop Fans/Start Wash Button

Exhaust Fan, Supply Fan and Optional

Continuous Cold Water Mist will stop

and allow the wash cycle to initiate.

Start Fan Light OFF

Does the

system have

the 24 Hour Timer

Option?

Are Manual

Shut-off

valves going

to be used?

Is this a single

hood or the last

hood to wash in a

sequence wash

system?

Do you

Want to

Bypass the

24 Hour Timer?

Hoods Automatic Fire Suppression System Activates

N.C. Contacts Open -One to activate waterwash system

fire mode, the other to disconnect the supply fan

Waterwash System Enters Fire Mode

Waterwash and Continuous Cold Water Mist Spray Water in

Hood Plenum. The Fan Circuit is activated. All Lights ON

Exhaust Plenum Drip Dry (1 min.)

Allows excess water

to drain from hood.

Stop Fan/Start Wash Light OFF

Fans Stop

Exhaust, Supply Fans and Optional

Continuous Cold Water Mist shut

down. Start Fan Light OFF.

Exhaust, Supply Fans and Optional

Continuous Cold Water Mist Activate

(1 min.) to exhaust heat and steam

built up in hood. Start Fan Light ON

Water Solenoid Valve Closes

Water solenoid valve remains open

for 30 sec. after the detergent

pump stops to allow detergent to

be purged from the line.

Detergent Pump Stops

Pump run time is factory set

at 4 Minutes. Consult page 26

to change pump run time.

Detergent Pump Activates

Detergent will be injected into the

water line

Cold Water Purge (15 sec.)

Water Solenoid Valve Opens o Allow

Cold Water to be Purged from the

Hot Water line.

Stop Fan/Start Wash Light ON.

24 Hour Timer

The Wash Cycle Will Begin at the

Preset Time.

Sequence Wash Delay To Allow

Water Heater to Regenerate.

Factory set at 15 Min.

Consult page 26 to Change Delay.

To Bypass the 24 Hour Timer

Press the Stop Fan/Start Wash

Button a Second Time.

YES

YES

YES

YES

NO

NO

NO

NO

Fig. 24

W

a
s
h

C

y

c

l

e

D

r

y

C

y

c

l

e

Advertising
This manual is related to the following products: