If it is necessary to place the power sources elsewhere, use a firm, dry and level surface. Try not

to allow dust or other impurities to enter the machines cooling air flow. Preferably site them

above floor level, for example on a suitable carriage unit.
Notes for positioning the machine

• The surface inclination should not exceed 15 degrees.

• Ensure the free circulation of the cooling air. There must be at least 20 cm of free space

in front of and behind the machine for cooling air to circulate.

• Protect the machine against heavy rain and direct sunshine.

NOTE!

Do not operate the machine in the rain. The protection class is IP23S, which allows for

outside preserving and storage only.

NOTE!

Never aim metallic grinding spray/sparks towards the equipment.

2.7

DISTRIBUTION NETWORK

All regular electrical devices without special circuits generate harmonic currents into

distribution network. High rates of harmonic current may cause losses and disturbance to

some equipment.

KempArc Pulse TCS:

This equipment complies with IEC 61000-3-12 provided that the short-circuit power S

sc

is greater than or equal to 5.5 MVA at the interface point between the user’s supply and

the public supply network. It is the responsibility of the installer or user of the equipment

to ensure, by consultation with the distribution network operator if necessary, that the

equipment is connected only to a supply with a short-circuit power S

sc

greater than or equal

to 5.5 MVA.