Nortec SE Series User Manual

Page 10

Advertising
background image

7 | Introduction

Table 3: SETC/P Specifications

Model

SETC

Part No

SEP

Part No.

CV

Valve

CV Valve,

Steam

Inlet, Wye

Port (NPT)

Cond-

ensate

Port

(NPT)

Net/Full

Weight

lb (kg)

Required

fill line

flow

gal (l)

/min

Required

Drain

capacity

gal (l)

/min

Electrical

50

2552765 2520383

2.8

1/2

3/4

125/180

(57/82)

2.6 (10)

5.2 (20)

Voltage

110-120

Phase

1

Amps

1.25 A

Power

0.15 KW

Max

Disconnect

15 A

100

2550073 2525132

5.5

3/4

3/4

267/423

(121/192)

175

2550074 2525133

10

1

3/4

250

2550075 2525134

12

1

3/4

355/599

(161/272)

375

2550076 2525135

20

1 1/4

3/4

525

2550077 2553312

28

1 1/2

1

529/992

(240/450)

750

2550078 2553313

40

2

1

4.5 (17)

8 (29)

1050 2550080 2525139

65

2 1/2

1 1/4

703/1384
(318/628)

Table 4: SETC/P Capacities and Water Consumption

Model

*Supply

Steam

Pressure

(psig)

*Max Output

lb/hr (kg/hr)

Approximate

Boiler Steam

Consumption

lb/hr (kg/hr)

**Water

Consumption

gal (l) /hr

**Drain Volume

gal (l) /hr

50

5

13 (6)

15 (7)

2.3 (9)

0.8 (3)

10

32 (14)

36 (16)

5.7 (21)

1.9 (7)

15

50 (23)

58 (26)

9.0 (34)

3.0 (11)

100

5

26 (12)

30 (14)

4.7 (18)

1.6 (6)

10

63 (29)

72 (33)

11.3 (43)

3.8 (14)

15

100 (45)

115 (52)

18.0 (68)

6.0 (23)

175

5

46 (21)

52 (24)

8.2 (31)

2.7 (10)

10

110 (50)

127 (58)

19.8 (75)

6.6 (25)

15

175 (80)

201 (91)

31.5 (119)

10.5 (40)

250

5

65 (30)

75 (34)

11.7 (44)

3.9 (15)

10

158 (72)

181 (82)

28.3 (107)

9.4 (36)

15

250 (114)

288 (131)

44.9 (170)

15.0 (57)

375

5

98 (44)

112 (51)

17.5 (66)

5.8 (22)

10

236 (107)

272 (123)

42.5 (161)

14.2 (54)

15

375 (170)

431 (196)

67.4 (255)

22.5 (85)

525

5

137 (62)

157 (71)

24.5 (93)

8.2 (31)

10

331 (150)

380 (173)

59.5 (225)

19.8 (75)

15

525 (239)

604 (274)

94.4 (357)

31.5 (119)

750

5

195 (89)

224 (102)

35.1 (133)

11.7 (44)

10

473 (215)

543 (247)

84.9 (321)

28.3 (107)

15

750 (341)

863 (392)

134.8 (510)

44.9 (170)

1050

5

273 (124)

314 (143)

49.1 (186)

16.4 (62)

10

662 (301)

761 (346)

118.9 (450)

39.6 (150)

15

1050 (477)

1208 (549)

188.7 (714)

62.9 (238)

*

Supply steam pressure must be present at the CV valve to achieve rated output

** At maximum output , 25% blow down, and with drain water cooling activated.

Advertising