Troubleshooting | 78

Code

Display

Message

LED

System Detected

Cause

Corrective Action(s)

FLF

Float Level

Red

More than one
Float Level is
registering at the
same time

1. Float chamber or

board not in place

1 Check that float board

is properly installed in
plastic support , that tie
wrap is in place, and
that float reservoir is in
place.

FLF

(Cont)

2 Float level sensor is

malfunctioning.

2 Squeeze bottom hose

from float chamber and
activate fill valve using
diagnostic output test.
Watch for proper light
sequence. Replace
assembly if sequence is
incorrect.

FTF

Fill Fault /

Warning

Red

The fill valve has
been active for
an extended
time without
reaching level 1.

1 Water supply off or

inadequate

1a Ensure water line is

open and that adequate
water supply and
pressure is available.

2 Fill valve strainer

blocked

2a Disconnect water

supply line and remove
strainer. Clear if
obstructed.

FTW

3 Fill Valve not activating 3a Check wiring to fill

valve.

3b Activate fill valve with

diagnostic output test.
Verify water is flowing
when activated.

4 Float board not

detecting water

4a Check wiring to float

board.

5 Manual drain switch on

or auxiliary drain open.

5a Check that manual

drain switch is not on.

5b Check that auxiliary

drain valve is closed.

HMF

Maint. Fault /

Warning

Red

The Humidifier
Maintenance
interval and 72
hour window for
cleaning has
expired

1 Humidifier requires

maintenance

1 Perform humidifier

maintenance as
described Maintenance
Schedule
on page 65

HMW

Yel

The preset
service interval
time has
expired.

2 Service reminder not

reset after
maintenance

2 Reset service reminder

as described in Reset
Service Reminder
on
page 50

KWF

Keep Warm

Fault

Red

Keep Warm
activated but
tank
temperature has
not increased
within time
allotted

1 Tank temperature

sensor not detecting
warm tank.

1a Check tank to see if hot

(caution).

1b Check wiring to tank

temperature sensor.

1c Check if sensor closed

when tank is hot.