E. see digital humidistat, Age 75, 75 blower pack – Nortec SE Series User Manual

Page 78: 75 digital humidistat, Blower pack, Digital humidistat

Advertising
background image

75 | Troubleshooting

Symptom

Cause

Corrective Action(s)

SAM-e Grommet leaks

1 Distributor tubes not seated

properly

1 Push distributor tubes down until

support washer is resting on rubber
grommet.

2 Grommet Damaged

2 Replace any damaged grommets

Blower Pack

Symptom

Cause

Corrective Action(s)

Blower not operating

Note: Blower pack does not
come on unless the humidifier
is producing steam.

1 No power to blower pack

1a Check power connection.
1b Check blower pack fuses

2 On/Off Thermostat not closing

2 Check wiring to thermostat replace if

it does not close when it is exposed
to steam.

Digital Humidistat

Symptom

Cause

Corrective Action(s)

Humidistat Reading incorrectly

1 Sensor out of calibration

1 Check reading against known

reliable instrument. If out of
calibration it can be field calibrated
±10%. Press

buttons together

until calH appears on the display.
Press

to display the current

calibration trim. Adjust using



buttons. Press  button when done.

2 Improper sensor location

2 Check that the humidistat is

positioned in a location
representative of room humidity.

3 Exposed to draft or heat source

3 Check that heat/cold fluctuations,

drafts, sunlight, doors, or vents are
affecting the reading.

4 No vapour barrier

4 Insure drafts cannot affect reading

by ensuing vapour barrier is in place
and working.

Advertising