79 | Troubleshooting

Code

Display

Message

LED

System Detected

Cause

Corrective Action(s)

KWF

(Cont)

2 No steam supply to

humidifier.

2a Check that isolation

valve is not closed.

2b Check if boiler steam is

available.

2c Check if CV valve opens

using diagnostic output
test.

3 Condensate not

draining from heat
exchanger.

3a Check that F&T trap is

allowing condensate to
drain.

LKF

Leak Fault /

Warning

Red

Float level has
dropped multiple
times while no
steam is being
produced.

1 Steam leaking through

CV valve

1a CV valve actuator not

adjusted. Follow Figure
11: CV Valve Actuator
Installation on page 16.

1a CV valve defective.

Replace CV valve.

LKW

2. Auxiliary drain is

leaking.

2a Check that auxiliary

drain valve is closed
and is not leaking.

3. Tank or fittings are

leaking.

3a Check for leaks from

tank, tank covers, and
fittings.

LMI

Limit Instable

Limit signal
Is not stable.

1 High limit humidistat

too close to steam
distributor

1 Locate the high limit

humidistat a minimum
of 10 feet (3 m) from
the distributor.

2 High limit humidistat

setpoint too low

2 Adjust the high limit

setpoint to 85% or
more.

3 Improper Proportional

and Integral settings in
control

3 Adjust proportional and

integral settings to
reduce swings in
demand signal.

4 Defective control

4 Replace defective

control

MEM

Flash R/W Fault

Red

Controller
Memory failure

1 Software has detected

a hardware problem
with main control
board

1 Restart humidifier, if

error occurs within 1
minute replace main
control board. If error
does not occur then
primary power
fluctuation may be the
cause.

MTW

ModBus
Timeout

No Modbus
signal

1 Loose connection

1 Check connections and

polarity of wires.

2 Incorrect Modbus

address

2 Check that Modbus

address of humidifier
matches that of master.