19 | Installation
Figure 14: Distributor Location in Duct
Figure 15: SAM-e/Steam Distributor Above Humidifier (Copper Steam Line Shown)
12 in.
(30 cm)
min.
Calculated absorption
distance to any obstruction
or 8-10 ft (2.4 - 3 m)
if unknown
Mount distributor
to side of duct
2 x duct
height min.
2/3 Duct
height
Note:
Refer to distributor or SAM-e installation manuals for detailed installation instructions.
Hose cuff
with clamps
2 in. (5 cm)
min.
1 ft (30 cm)
‘P’ Trap
1 ft (30 cm)
min. before
anybend
Condensate line
Use steam hose between
steam outlet and steam line.
Insulated copper
steam line. Support
so weight is not on
steam outlet.
To drain