background image

Installation | 12

Mounting on Optional Stand

The optional SE floor stand positions the SE humidifier at a convenient working height and
provides additional clearances for sloping drains. The stand must be assembled at site.

Assemble the stand according to the instructions that are provided with it.

Ensure the stand and humidifier are installed on a level surface

Permanently secure the stand to the floor via the holes in the leg support plates following

any local codes or regulations.

Figure 7: Mounting on Optional Stand

Note: The humidifier must be secured to the stand (hardware provided) and the stand

must be secured to the floor (hardware by others).

Center support only
present on SE 525
and larger.

Fasten SE humidifier

to stand with bolts,

lock washers, and nuts

provided. Tighten

to 200 in-lb (22.6 Nm).

Mount stand on level surface

Ensure humidifier is Level

Secure stand to floor
four places.
(hardware by others)