57 | Operation

(Control Settings Continued)

Supply Press
Sets the steam supply pressure for
the humidifier to us in displaying its
steam output. It is only displayed if
Press Based is set to On. (Default =
15 psi)

RH Settings

The RH Settings submenu is used to adjust setpoint, the proportional band, and the integral
time if REG Mode is set to RH (P) or RH (PI) and the humidifier is connected to humidity sensors.
Access the RH Settings submenu by pressing the menu key while RH Settings is highlighted in
the Control Settings menu.


CNT Set-P
Sets the humidity setpoint value.
The humidifier will attempt to
maintain this humidity level in the
space where the control transducer
is installed.

CNT Band should not normally be
changed. The CNT Band setting
adjusts the band within which the
humidifier will modulate between 0
and 100% output. (Default = 15%)

Int Time should not normally be
changed. Int Time adjusts the
frequency at which the controller
corrects for proportional control
error. It is only displayed if REG Mode
is set to RH (PI) (Default = 5 min)

Supply Press.

: 15 psi

Supply Pressure
15 psi

15 psi

Menu

Set

15 psi

Control Set Point
40% RH

40% RH

Menu

Set

CNT Set-P

: 40%

40% RH

Control Band
15% RH

15% RH

Menu

Set

CNT Band

: 15% RH

15% RH

Note: The RH Settings menu selection will only be displayed in the Control Settings

menu if REG Mode is set to RH (P) or RH (PI).

RH Settings
CNT Set-P

: 40% RH

CNT Band

: 15% RH

CNT Itime

: 5 min

LIM Set-P

: 80% RH

LIM Band

: 15% RH

LIM Damp

: 5 s

RH Alerts

: On

RH High

: 75% RH

RH Low

: 33% RH

Menu

Set

CNT Set-P

: 40%

RH Settings

Only present if RH Alerts is set to On

Only present if MOD Mode is set to Dual CH

Control Integral Time
5 min

5 min

Menu

Set

CNT Itime

: 5 min

5 min