74 steam distributors, 74 sam-e, Steam distributors – Nortec SE Series User Manual

Page 77: Sam-e

Advertising
background image

Troubleshooting | 74

Steam Distributors

Symptom

Cause

Corrective Action(s)

Distributor spitting out water

1 Distributor not level

1 Use support at end o distributor to

ensure it is level.

2 “P” Trap too close to distributor

2 “P” Trap must be a minimum of 12 in

(30 cm) below the distributor to
ensure flow. Relocate if required.

3 Condensate line not sloped

sufficiently

3 Sufficient slope to insure flow is

required. Reinstall if required.

4 Trap blocked

4 Check that water flows through trap.

Clear out if blocked.

5 Condensate line double trapped

5 Condensate lines must not have two

traps in sequence. This can cause an
air lock and prevent water draining.

6 Steam line not insulated

6 If steam line is long condensate build

up could overload distributor
condensate port. Insulate line to
improve efficiency and install
additional condensate traps as
required.

Condensation in duct

1 Installation clearances not

observed

1 Refer to distributor installation

manual for required clearances.
Relocate distributor if required.

2 Design conditions changed

2 Check supply air temperature and

humidity to determine if conditions
have changed.

3 High limit not functioning

3 Check setting and operation of high

limit. Replace if defective.

4 Air proving not installed or not

working

4 Check that the humidifier will only

operate when there is air moving in
the duct.

5 Improper location of high limit

5 Check that high limit is installed

where it can detect high duct
humidity.

SAM-e

Symptom

Cause

Corrective Action(s)

SAM-e spitting out water

1 “P” Trap too close to SAM-e

1 “P” trap must be at least 12 in (30

cm) below header. Relocate if
required.

2 Condensate line not sloped

sufficiently

2 Ensure line is sloped sufficiently to

carry condensate produced.

3 Steam line not insulated

3 If steam line is long condensate build

up could overload the SAM-e
condensate port. Insulate the steam
line to improve efficiency and install
condensate traps as required.