Troubleshooting the pt-link ii controller, Pt-link ii bacnet, Technical guide pt-link ii interface 18 – Orion System PT-Link II BACnet2 User Manual
Page 18: Using ruinet, Verifying proper communications, Verifying proper values

PT-Link II BACnet
®
Technical Guide
PT-Link II Interface
18
Troubleshooting the PT-Link II Controller
Figure 29: Data Array Overview Screen
Using RUINET
Before continuing with the troubleshooting, make sure the PT-Link is
connected correctly and the RUINET software is installed, running, and
functioning correctly.
Verifying Proper Communications
From the RUINET Main Screen, press
<O>
to go the Connection
Overview Screen. This screen supplies information on communication
between the PT-Link and remote devices. A number of aspect screens
are available, and some of the aspect screens have more than one page.
Use the space bar to toggle between aspects and use the
<PgUp>
and
<PgDn>
keys to toggle between pages of the same aspect. The Con-
nection Overview and Settings Aspect Screen is shown in Figure 28.
The main purpose in this screen is to verify that messages and characters
are being transmitted and received. In addition, it shows the number of
communication errors. If the PT-Link connection “03” is the protocol
connection, verify that is communicating appropriately. If it is not, check
that the PT-Link LEDs are working properly, the unit is wired correctly,
and the PT-Link is confi gured correctly (Baud Rate, Unit Address &
MAC Address). If the number of errors is constantly increasing, move
to the Error Screen by pressing the
<Space Bar>
3 times to fi nd out
the cause of the errors. Use the
<PgUp>
and
<PgDn>
keys to toggle
between pages of the Error Screen.
Verifying Proper Values
To verify that the correct values for each unit are being communicated
to the PT-Link, move to the Data Array Overview Screen. To get to the
screen, press
<A>
from the RUINET Main Menu. See Figure 29 for
screen details.
In the Data Array Overview Screen (Figure 29) you will be able to see
the data arrays of all the units connected to the PT-Link denoted by an
array name “DA_XXX_IY”—Y being the address of the unit minus
one. The Address of the unit is determined by a set of DIP switches.
To view the values being communicated from a specifi c unit, move to
the Data Array Detail Screen (Figure 30) of the unit by entering the
number under which it is listed. For example, for the unit listed in the
third position, enter
<03>
.
To understand what each value means, look at the Data Array Tables
for the desired unit type, VCM-X, SA, or VCM. You can change the
writable values from this screen by using the modify command. To use
the modify command, press
<M>
from the Data Array Detail Screen
and then enter the Offset you want to change followed by a space and
the new value.
Example: To change the Cooling Supply Setpoint to 60 in the VCM, press
<M>
, enter
<58 60>
, and then press
<Enter>
. This could be useful to
prove that the unit can take and keep the setpoints properly.
Figure 28: Connection Overview Screen
Figure 30: Data Array Detail Screen