Appendix f - vcm-x bacnet parameters, Pt-link ii bacnet, Technical guide pt-link ii interface 42 – Orion System PT-Link II BACnet2 User Manual

Page 42

Advertising
background image

PT-Link II BACnet

®

Technical Guide

PT-Link II Interface

42

Appendix F - VCM-X BACnet Parameters

BACnet Properties for the VCM-X Controller

Parameter

Name

Object

Description

Limits

Alarm

Status

AlmSts

AI: 1

See Alarm

Group Bits on

page 47.

Control

Status

CtrlSts

AI: 4

Current operational

status.

Occupied/

Mode

Enable

Cooling

Setpoint

Mirror

ClSt

AI: 7

Occupied/ Mode

Enable Cooling

Setpoint Mirror.

Control

Temperature

CtrlTp

AI: 9

Current value of the

control temperature

sensor.

Duct Static

Pressure

DuctPr

AI: 14

Current value of the

duct static pressure

sensor.

Economizer

Position

EcoPos

AI: 16

Current position

of the economizer

damper.

Occupied/

Mode

Enable

Heating

Setpoint

Mirror

HtSt

AI: 31

Occupied/ Mode

Enable Heating

Setpoint

Mirror.

Modulating

Gas Valve

Position

MdHt-

2Pos

AI: 38

Current position

of MODGAS II

modulating gas

valve control.

On Board

Relays

OnRlys

AI: 44

See page 47.

Outdoor Air

Dewpoint

OaDwpt

AI: 47

Current calculated

outdoor air

dewpoint added on

version 1.09.

Outdoor Air

Humidity

OaRh

AI: 52

Current value of the

outdoor humidity

sensor.

Outdoor Air

Temperature

OaTp

AI: 54

Current value of the

outdoor tempera-

ture sensor.

Outdoor Air

Wetbulb

OaWtbl

AI: 55

Current calculated

value of the outdoor

wetbulb

temperature.

Reheat

Value

Position

Rt2Pos

AI: 60

Current position of

MHGRV modulat-

ing hot gas reheat

valve control.

Relief

Pressure

RfPr

AI: 62

Current value of the

building pressure

sensor.

Return Air

Temperature

RaTp

AI: 64

Current value of the

return temperature

sensor.

BACnet Properties for the VCM-X Controller

Parameter

Name

Object

Description

Limits

Indoor

Humidity

InRh

AI: 67

Current value of

the indoor humidity

sensor.

Space

Temperature

SpcTp

AI: 72

Current value of the

space temperature

sensor.

Current

Supply Air

Setpoint

SaTpStM

AI: 82

Current SAT

Cooling or Heating

setpoint if there

is no reset source;

Current calculated

SAT setpoint with

Reset Source.

Supply Air

Temperature

SaTp

AI: 83

Current value of the

supply air

temperature sensor.

Temperature

Demand

TpDmnd

AI: 84

Based on the

comparison

between the

current Control

Temperature and

the Heating or

Cooling Setpoint

Temperatures. Does

not work for supply

air control

VFD

Blower Fan

VfdBw-

Pos

AI: 88

Current position of

the VFD blower fan

signal.

VFD

Relief Fan

VfdExPos

AI: 89

Current position of

the VFD relief

fan signal.

Application

Software

Version

AppVer

AI: 99

Current version of

the software in the

unit.

Alarm

Group 1

AlrmGrp1

AI: 104

See Alarm

Group Bits on

page 47.

Alarm

Group 2

AlrmGrp2

AI: 105

See Alarm

Group Bits on

page 47.

Alarm

Group 3

AlrmGrp3

AI: 106

See Alarm

Group Bits on

page 47.

Dewpoint

Setpoint

Mirror

DptStM

AI: 110

Mirror of the DPtSt

“read only.”

External

Relays 1-2

ExRlys12

AI: 111

See page 47.

External

Relays 3-4

ExRlys34

AI: 112

See page 47.

Indoor Rh

Setpoint

Mirror

InRhStM

AI: 114

Mirror of the

InRhSt “read only.”