Appendix d - vcb-x bacnet parameters, Pt-link ii interface pt-link ii bacnet, Technical guide 39 vcb-x pt-link ii bacnet – Orion System PT-Link II BACnet2 User Manual
Page 39: Property identifi er

PT-Link II Interface
PT-Link II BACnet
®
Technical Guide
39
VCB-X PT-Link II BACnet
®
Property Identifi er:
The PT-Link II BACnet
®
Link amends the following property identity
to the BACnet
®
property identifi er.
BACNETPropertyIdentifi er :
VcbxUnitMode ::= ENUMERATED {
Unoccupied
(0)
Occupied
(1),
Override
Mode
(2),
Holiday
Unoccupied
(3),
Holiday
Occupied
(4),
Forced
Occupied
(5),
Forced
Unoccupied
(6),
}
VcbxControlStatusBits ::= ENUMERATED {
Off
(0),
Vent
Mode
(1),
Cooling
Mode
(2),
Heating
Mode
(3),
Vent
RH
Mode (4),
Cooling
RH
Mode
(5),
Heating
RH
Mode
(6),
Warm
Up
Mode
(7)
Defrost
Mode
(8)
Purge
Mode
(9)
}
VcbxAlarmGroup1Bits ::= BIT STRING {
Bad
Supply
Air
Sensor
(0),
Bad
Return
Air
Sensor
(1),
Bad
Outside
Air
Sensor
(2),
Bad
Space
Sensor
(3),
Bad Main Expansion Board
(4),
Bad
Coil
Temp
Sensor
(5),
Bad
Co2
Sensor
(6),
Bad
Discharge
Sensor
(7),
Bad
OA
CFM
Sensor
(8),
Bad Exhaust CFM Sensor
(9),
Bad Supply CFM Sensor
(10),
Bad
Return
CFM
Sensor
(11),
Bad
Reheat
Module (12),
Bad
ModGas
Module
(13),
Bad Relay Expansion Module
(14)
}
VcbxAlarmGroup2Bits ::= BIT STRING {
Mechanical Cooling Failure
(0),
Mechanical
Heating
Failure
(1),
Fan
Proving
Alarm
(2),
Dirty
Filter
Alarm
(3),
Emergency
Shutdown
Alarm
(4)
}
VcbxAlarmGroup3Bits ::= BIT STRING {
High Supply Air Cutoff
(0),
Low
Supply
Air
Cutoff
(1),
High Control Mode Signal Alarm
(2),
Low Control Mode Signal Alarm
(3),
Digital Compressor Cutoff Alarm
(4),
Digital Compressor Lockout Alarm
(5),
High
Head
Pressure (6)
}
VcbxOnBoardRelaysBits ::= BIT STRING {
On
Board
Relay
1
(0),
On
Board
Relay
2
(1),
On
Board
Relay
3
(2),
On
Board
Relay
4
(3),
On
Board
Relay
5
(4)
On
Board
Relay
6
(5)
}
Appendix D - VCB-X BACnet Parameters