Pt-link ii interface pt-link ii bacnet, Technical guide 41 – Orion System PT-Link II BACnet2 User Manual
Page 41

PT-Link II Interface
PT-Link II BACnet
®
Technical Guide
41
Appendix E - VCM-X Modular and WSHP BACnet Parameters
BACnet Properties for VCM-X WSHP (Coil)
Parameter
Name
Object
Description
Limits
Modulating
Compressor 2
MdCmp2
AI: 206
Current
position of the
2nd Stage of
Compressor
Modulation.
Head Pressure 1
HdPr1
AI: 207
Head Pressure
for
1st
Compressor
Head Pressure 2
HdPr2
AI: 208
Head Pressure
for
2nd
Compressor
Condenser
Fan 1
CdFan1
AI: 209
Condenser
Fan 1
Signal Status
Condenser
Fan 2
CdFan2
AI: 210
Condenser
Fan 2
Signal Status
BACnet Properties for VCM-X WSHP (Tulsa)
and RNE Controllers
Parameter
Name
Object
Description
Limits
Low Water
Temperature 1
Alarm
LWT1Alm
BI: 230
Alarm that
indicates water
temperature is
below the
Leaving Water
Safety Setpoint
(Heating only)
for System A.
Low Water
Temperature 2
Alarm
LWT2Alm
BI: 231
Alarm that
indicates water
temperature is
below the
Leaving Water
Safety Setpoint
(Heating only)
for System B
Proof of Water 1
Flow Alarm
POWF1Alm
BI: 232
Alarm that
indicates no
Proof of Water
Flow for System
A (A1/A2)
Proof of Water 2
Flow Alarm
POWF2Alm
BI: 233
Alarm that
indicates no
Proof of Water
Flow for System
B (B1/B2)
Module
Communica-
tions Alarm
ComMAlm
BI: 234
Alarm that
indicates that one
or more Modules
are not
communicating
with the VCM-X
WSHP Control-
ler.
BACnet Properties for VCM-X WSHP (Coil)
Parameter
Name
Object
Description
Limits
Water Temp. A
WaterTpA
AI: 220
Current water
temperature.
Remote VFD
Reset
RmVFDPos
AV:
258
Remote VFD
Position Reset
-1
100
Compressor A
Low Suction
Pressure Alarm
A1LSPAlm
BI: 222
Alarm that
indicates
Suction
Pressure for
Circuit A is
below the
Low
Suction Pres-
sure Cooling
(Heating)
Setpoint.
Compressor A
Lockout Alarm
A1LktAlm
BI: 223
Alarm that
indicates
Circuit A
Compressors
are locked
out.
Compressor B
Low Suction
Pressure Alarm
B1LSPAlm
BI: 226
Alarm that
indicates
Suction
Pressure for
Circuit B is
below the
Low
Suction Pres-
sure Cooling
(Heating)
Setpoint.
Compressor B
Lockout Alarm
B1LktAlm
BI: 227
Alarm that
indicates
Circuit B
Compressors
are locked
out.
Low Water
Temperature
Alarm
LWT1Alm
BI: 230
Alarm that
indicates wa-
ter tempera-
ture is below
the Leaving
Water Safety
Setpoint
(Heating
only).
Proof of Water
Flow Alarm
POWF1Alm
BI: 232
Alarm that
indicates no
Proof of Water
Flow.
Module
Communica-
tions
Alarm
ComMAlm
BI: 234
Alarm that
indicates that
one or more
Modules are
not commu-
nicating with
the VCM-X
WSHP
Controller.
Revised 10/11/12