Pt-link ii interface pt-link ii bacnet, Technical guide 41 – Orion System PT-Link II BACnet2 User Manual

Page 41

Advertising
background image

PT-Link II Interface

PT-Link II BACnet

®

Technical Guide

41

Appendix E - VCM-X Modular and WSHP BACnet Parameters

BACnet Properties for VCM-X WSHP (Coil)

Parameter

Name

Object

Description

Limits

Modulating

Compressor 2

MdCmp2

AI: 206

Current

position of the

2nd Stage of

Compressor

Modulation.

Head Pressure 1

HdPr1

AI: 207

Head Pressure

for
1st

Compressor

Head Pressure 2

HdPr2

AI: 208

Head Pressure

for

2nd

Compressor

Condenser

Fan 1

CdFan1

AI: 209

Condenser

Fan 1

Signal Status

Condenser

Fan 2

CdFan2

AI: 210

Condenser

Fan 2

Signal Status

BACnet Properties for VCM-X WSHP (Tulsa)

and RNE Controllers

Parameter

Name

Object

Description

Limits

Low Water

Temperature 1

Alarm

LWT1Alm

BI: 230

Alarm that

indicates water

temperature is

below the

Leaving Water

Safety Setpoint

(Heating only)

for System A.

Low Water

Temperature 2

Alarm

LWT2Alm

BI: 231

Alarm that

indicates water

temperature is

below the

Leaving Water

Safety Setpoint

(Heating only)

for System B

Proof of Water 1

Flow Alarm

POWF1Alm

BI: 232

Alarm that

indicates no

Proof of Water

Flow for System

A (A1/A2)

Proof of Water 2

Flow Alarm

POWF2Alm

BI: 233

Alarm that

indicates no

Proof of Water

Flow for System

B (B1/B2)

Module

Communica-

tions Alarm

ComMAlm

BI: 234

Alarm that

indicates that one

or more Modules

are not

communicating

with the VCM-X

WSHP Control-

ler.

BACnet Properties for VCM-X WSHP (Coil)

Parameter

Name

Object

Description

Limits

Water Temp. A

WaterTpA

AI: 220

Current water

temperature.

Remote VFD

Reset

RmVFDPos

AV:
258

Remote VFD

Position Reset

-1

100

Compressor A

Low Suction

Pressure Alarm

A1LSPAlm

BI: 222

Alarm that

indicates

Suction

Pressure for

Circuit A is

below the

Low

Suction Pres-

sure Cooling

(Heating)

Setpoint.

Compressor A

Lockout Alarm

A1LktAlm

BI: 223

Alarm that

indicates

Circuit A

Compressors

are locked

out.

Compressor B

Low Suction

Pressure Alarm

B1LSPAlm

BI: 226

Alarm that

indicates

Suction

Pressure for

Circuit B is

below the

Low

Suction Pres-

sure Cooling

(Heating)

Setpoint.

Compressor B

Lockout Alarm

B1LktAlm

BI: 227

Alarm that

indicates

Circuit B

Compressors

are locked

out.

Low Water

Temperature

Alarm

LWT1Alm

BI: 230

Alarm that

indicates wa-

ter tempera-

ture is below

the Leaving

Water Safety

Setpoint

(Heating

only).

Proof of Water

Flow Alarm

POWF1Alm

BI: 232

Alarm that

indicates no

Proof of Water

Flow.

Module

Communica-

tions

Alarm

ComMAlm

BI: 234

Alarm that

indicates that

one or more

Modules are

not commu-

nicating with

the VCM-X

WSHP

Controller.

Revised 10/11/12