Setting up your pt-link ii, Pt-link ii bacnet, Technical guide pt-link ii interface 4 – Orion System PT-Link II BACnet2 User Manual

Page 4: Quick guide, Figure 1: pt-link ii bacnet, Dimensions and components

Advertising
background image

PT-Link II BACnet

®

Technical Guide

PT-Link II Interface

4

Setting Up Your PT-Link II

Figure 1: PT-Link II BACnet

®

Dimensions and Components

485

DRIVER

COMM

R

SH

T

LOOP

PROTO

LED1

LED2

TIMER

W_DOG

H-BEAT

POWER

MADE IN USA

4.82

4.70

0.27

4.31

1.31

2.61

4.25

2.37

0.20 Dia.
Mounting Hole
Typ. 3 PL.

BACnet

®

Communications
Wiring Terminal

Local Loop
Communications
Wiring Terminal

Local Loop
Communications
Driver Chip

24 VAC Power
Terminal

Communications
LED

Diagnostic
LED #1

Diagnostic
LED #2

BACnet

®

Protocessor
Module

Power
LED

USB
Port

Ethernet
Port

www.orioncontrols.com

WattMaster Label

#LB102082

Rev. 01A

OE368-23B-BACNET

PT-LINK II PROTOCOL

TRANSLATOR

FOR BACNET

+24

VAC

GND

LOOP

LED 1

LED 2

=RAPID BLINK

=BLINKS QTY

CONTROLLERS

= STEADY BLINK

PROTO

TIMER

WATCH DOG

H-BEAT

=RAPID BLINK

= STEADY BLINK

= ON SOLID

= STEADY BLINK

LED BLINK CODES (NORMAL)

P

ROTO

C

E

SSO

R

Protocol

Copr

o

c

e

s

s

o

r

www.protoces

s

o

r.c

o

m

1

2

3

4

5

6

7

8

O

N

O

N

1

2

3

4

ON

RX

TX

RSGND

Configuration
DIP Switches

Quick Guide

The following steps will get you up and running in no time:

1.

Familiarize yourself with the PT-Link II components (Figure 1).

2.

Connect your PT-Link II to the Controller(s) on your system (up

to four) and connect your PT-Link II to the BACnet Network

(Figure 2).

3.

If the BACnet address doesn’t need to be any higher than 255,

then you can use the DIP switch settings to confi gure your PT-

Link II. Skip to page 9. Set the DIP Switches, wait 4 minutes,

and you’ll be up and running. If the address needs to be higher

than 255, or your BACnet module does not have DIP switches,

continue

with

Step 4.

4.

Copy the contents of the PT Link II CD to your PC’s Desktop.

You can also download the fi les from http://orioncontrols.com/

software-new.html under PT-Link II Setup Files. These fi les

include

RUINET.

5.

Connect your PT-Link II to your computer using an Ethernet

connection

(Figures 3 & 4).

6.

Change your PCs IP Address. Follow the directions that match

your current operating system - Windows NT, XP, Vista, or 7.

See directions on pages 7 & 8.

7.

Obtain the following from your Building Automation System

Integrator: the BACnet MAC address (System Node ID), your

server’s baud rate, and the Client Node ID.

8.

Using RUINET, edit the Confi g.csv fi le and verify PT Link II

communications. Follow the directions on pages 10-13.

9.

If you run into any problems, follow the instructions in the

Troubleshooting section starting on page 14 of this guide.

Revised 5/11/11