PT-Link II BACnet

®

Technical Guide

PT-Link II Interface

34

Appendix D - VCB-X BACnet Parameters

BACnet Properties for the VCB-X Controller

Parameter

Name

Object

Description

Limits

Low Coil

Temperature

Setpoint

LoClTpSt

AV:295

This is the

lowest that the

Coil

Temperature

will be reset to

during Space

Humidity Reset

of the Coil

Suction

Temperature

Setpoint.

Produces a

dewpoint in

the supply air

approximately

10˚F above this

setpoint.

35

70

Condenser

Control Signal

CdCtrSg1

AI:280

Condenser Fan

Signal 1 Status.

Control Status

CtrlSts

AI: 4

Current

operational

status.

See Control

Status Bits on

page 39.

Control

Temperature

CtrlTp

AI: 9

Current value

of the control

temperature

sensor.

Cooling
Enabled

ClEnbl

AI: 6

Status that

indicates

mechanical

cooling is

enabled.

Cooling

Setpoint

Mirror

ClSt

AI: 7

Occupied

Cooling Mode

Enable

Setpoint Mirror.

Dewpoint

Setpoint

RhDewpSt

AV:282

On a MUA unit,

if the outdoor

dewpoint rises

above this

setpoint, the

unit will

activate Dehu-

midifi cation.

35

80

Economizer

Enabled

EcoEnbl

AI: 15

Status that

indicates

the economizer

is enabled.

Economizer

Enable

Setpoint

EcoEnbSt

AV:283

The economizer

is enabled if the

outdoor dry-

bulb, dewpoint,

or wetbulb

temperature

falls below this

setpoint.

-30

80

Economizer

Position

EcoPos

AI: 16

Current

position of the

economizer

damper.

BACnet Properties for the VCB-X Controller

Parameter

Name

Object

Description

Limits

Minimum

Economizer

Position

MinEcoSt

AV: 151

This is the

minimum

position of the

economizer in

the occupied

mode.

0

100

Force

Economizer

FrcEcono

AV: 267

Overrides all

other Outdoor

Air Damper

position com-

mands so as to

maintain this

fi xed position.

Confi guring

for “Auto” will

restore normal

unit control of

the Outdoor

Air Damper/

Economizer

operation.

0%

100%

Auto=65535

Exhaust Fan

CFM

EtCFM

AI:194

Current

Exhaust

Airfl ow

Measurement

Exhaust Fan

Speed

EtFnSpd

AI: 273

Current

position of the

VFD relief

fan signal.

Fan

Starting Delay

FanDly

AI: 25

Indicates the

current fan

status related

to request to

run, fan starting

delay or POF

failure.

0=No Request

1=Fan

Running

2=Fan Start

Delay

3=POF Failure

Force HVAC

Mode

FrcHvacM

AV: 262

Overrides

normal control-

ler operation in

order to force

the unit into

this desired

mode. Con-

fi guring for

“Auto” will

restore normal

unit control of

the mode of

operation.

0=Auto

1=Vent

2=Cool
3=Heat

4=Vent

Dehum.

5=Cool

Dehum.

6=Heat

Dehum.

Head

Pressure

HeadPr

AI:276

Current value

of the Head

Pressure

Reading.

Head

Pressure
Setpoint

HeadPrSt

AI:279

Current Head

Pressure

Setpoint.