General information, Pt-link ii interface 3 pt-link ii bacnet, Technical guide – Orion System PT-Link II BACnet2 User Manual

Page 3: Data sharing, Scheduling, Hardware specifi cations, System requirements

Advertising
background image

PT-Link II Interface

3

PT-Link II BACnet

®

Technical Guide

The OE368-23B-BACNET2, PT-Link II BACnet

®

provides bi-direction-

al communication between your BACnet

®

MS/TP protocol network and

up to four* of any of the following types of Orion controllers—RNE,
VCB-X, VCM-X, SA, VCM, MUA II, or VAV/CAV:

RNE Controller (SS1045)

VCB-X Controller (SS1051)

VCM-X Controller (SS1026, SS1030, SS1032, SS1033,
SS1034, Y200920)

SA Controller (Y200921)

VCM Controller (SS1016, Y200409, Y200616, Y200822)

**MUA II Controller (Y200405); VAV/CAV Controller
(Y200301)

To determine what controller you have, you must look at the label located
on the controller EPROM. If the controller label does not match any of
the SS or Y numbers listed above, your controller will not work with
the PT-Link II BACnet

®

.

*NOTE: The PT-Link II BACnet

®

device can be used to con-

nect to four Orion controllers. If more than four Orion
controllers are present in a system, you will need one
or more additional PT-Link II BACnet

®

devices for

integration with a BACnet

®

protocol network.

**

NOTE: Documentation is available for MUA II/VAV/CAV on

our Orion Controls website: www.orioncontrols.com/
literature-new.html

Data Sharing

The PT-Link II BACnet

®

interface provides the following data sharing

capabilities:

Provides values from points on the Orion side of the

gateway to BACnet

®

devices as if the values were

originating from BACnet

®

objects.

Allows BACnet

®

devices to modify point values on the

Orion controller side of the PT-Link II BACnet

®

by using

standard

BACnet

®

write services.

Scheduling

Ability to allow BACnet

®

devices to send Schedule events

to the Orion controller side of the gateway by using

standard

BACnet

®

services.

Hardware Specifi cations

Table 1 contains the hardware specifi cations for the PT-Link II BACnet

®

interface.

Technical Data

BACnet®-MS/TP Loop

9600, 19200, 38400, 76800 Mbps

Controller Loop

RS-485, 9600 Baud Rate

Network Protocol

BACnet®

Protocol
(WattMaster Loop)

HSI Open Protocol Token Passing

Power Input Voltage

24 VAC

Power Consumption

10 VA Maximum

Operating Temp

-30°F to 150°F

Operating Humidity

90% RH Non-Condensing

Weight

4.5 oz.

Table 1: PT-Link II BACnet

®

Interface

Technical Data

System Requirements

The

PT-Link II BACnet

®

interface is packaged and

assembled as surface mount. Surface mount components

are included for your convenience.

Computer running Microsoft Windows

TM

operating

system.

Ethernet Crossover Cable (supplied).

PT-Link II BACnet software—located on included CD-

ROM and downloadable from www.orioncontrols.com/

software-new.html.

• *

RUINET software— located on included CD-ROM and

downloadable from www.orioncontrols.com/software-new.

html.

*NOTE:

RUINET is only needed for initial confi guration if you

need to set the address above 255 or if your BACnet
lacks DIP switches. The confi g.csv fi le’s Server_DIP
parameter is initially set to Enabled which allows
the System_Node_ID (BACnet MAC Address) and
Node_ID (Device Instance) to be set using the DIP
Switches on the module.