Appendix D - VCB-X BACnet Parameters

Revised 1/20/12

BACnet Properties for the VCB-X Controller

Parameter

Name

Object

Description

Limits

Occupied

Heating

Setpoint

OcpHtSt

AV: 43

If the control

temperature

drops one

degree below

this setpoint,

the control

will activate

the heating

demand. If the

control

temperature

is the Supply

Air Sensor, then

there is no

heating

demand.

1

110

Hood On

Outdoor

Air Cooling

Setpoint

OaClSt

AV:45

This is the

Cooling Mode

Enable

Setpoint used

only in Hood

On Mode.

1

110

Hood On

Outdoor

Air Heating

Setpoint

OaHtSt

AV:46

This is the

Heating Mode

Enable

Setpoint used

only in Hood

On Mode.

1

110

Outdoor Air

CFM

OaCFM

AI: 193

Current Out-
door Airfl ow

Measurement

Minimum

Desired

Outdoor Air

CFM

OACfmMin

AV:291

Minimum Out-

door Airfl ow

CFM Setpoint

.10K

200K

Outdoor

Humidity

OaRh

AI:52

Current value

of the Outdoor

Humidity

Sensor.

Outdoor Air

Temperature

OaTp

AI: 54

Current value

of the

outdoor

temperature

sensor.

Outdoor Air

Temperature

Offset

OaTpOst

AV: 53

If the

Outdoor

Temperature

Sensor is

reading

incorrectly, you

can use this

option to

enter an offset

temperature to

adjust the

Sensor’s

Temperature.

-100

100

BACnet Properties for the VCB-X Controller

Parameter

Name

Object

Description

Limits

Preheat

Relay

Setpoint

PreHtAmb

AV:286

If the Supply

Fan is ener-

gized this is the

temperature

at which the

Preheat Relay

will activate.

Operates in

the Occupied

or Unoccupied

Mode.

-30

70

Reheat Valve

Position

RtVlvPos

AI:277

Current

position of

MHGRV

modulating

hot gas reheat

valve.

Return Air

CFM

RaCFM

AI:275

Current Return

Airfl ow

Measurement.

Return Air

Temperature

RaTp

AI: 64

Current value

of the return

temperature

sensor.

Return Air

Temperature

Sensor Offset

RaTpOst

AV: 65

If the Return

Temperature

Sensor is

reading

incorrectly, you

can use this

option to

enter an offset

temperature to

adjust the

Sensor’s

Temperature.

-100

100

Schedule

Force

SchdFrc

AV: 66

0 = Auto (uses

controller’s

schedule)

1 = Forced

Occupied

2 = Forced

Unoccupied

0

2

Space

Temperature

SpcTp

AI:72

Current value

of the space
temperature

sensor.

Space

Temperature

Offset

SpcTpOst

AV:71

If the Space

Temperature

Sensor is

reading

incorrectly, you

can use this

option to enter

an offset

temperature to

adjust the

Sensor’s

Temperature.

-100

100

Static

Pressure

StaticPr

AI:270

Current Static

Pressure.