Appendix D - VCB-X BACnet Parameters
Revised 1/20/12
BACnet Properties for the VCB-X Controller
Parameter
Name
Object
Description
Limits
Occupied
Heating
Setpoint
OcpHtSt
AV: 43
If the control
temperature
drops one
degree below
this setpoint,
the control
will activate
the heating
demand. If the
control
temperature
is the Supply
Air Sensor, then
there is no
heating
demand.
1
110
Hood On
Outdoor
Air Cooling
Setpoint
OaClSt
AV:45
This is the
Cooling Mode
Enable
Setpoint used
only in Hood
On Mode.
1
110
Hood On
Outdoor
Air Heating
Setpoint
OaHtSt
AV:46
This is the
Heating Mode
Enable
Setpoint used
only in Hood
On Mode.
1
110
Outdoor Air
CFM
OaCFM
AI: 193
Current Out-
door Airfl ow
Measurement
Minimum
Desired
Outdoor Air
CFM
OACfmMin
AV:291
Minimum Out-
door Airfl ow
CFM Setpoint
.10K
200K
Outdoor
Humidity
OaRh
AI:52
Current value
of the Outdoor
Humidity
Sensor.
Outdoor Air
Temperature
OaTp
AI: 54
Current value
of the
outdoor
temperature
sensor.
Outdoor Air
Temperature
Offset
OaTpOst
AV: 53
If the
Outdoor
Temperature
Sensor is
reading
incorrectly, you
can use this
option to
enter an offset
temperature to
adjust the
Sensor’s
Temperature.
-100
100
BACnet Properties for the VCB-X Controller
Parameter
Name
Object
Description
Limits
Preheat
Relay
Setpoint
PreHtAmb
AV:286
If the Supply
Fan is ener-
gized this is the
temperature
at which the
Preheat Relay
will activate.
Operates in
the Occupied
or Unoccupied
Mode.
-30
70
Reheat Valve
Position
RtVlvPos
AI:277
Current
position of
MHGRV
modulating
hot gas reheat
valve.
Return Air
CFM
RaCFM
AI:275
Current Return
Airfl ow
Measurement.
Return Air
Temperature
RaTp
AI: 64
Current value
of the return
temperature
sensor.
Return Air
Temperature
Sensor Offset
RaTpOst
AV: 65
If the Return
Temperature
Sensor is
reading
incorrectly, you
can use this
option to
enter an offset
temperature to
adjust the
Sensor’s
Temperature.
-100
100
Schedule
Force
SchdFrc
AV: 66
0 = Auto (uses
controller’s
schedule)
1 = Forced
Occupied
2 = Forced
Unoccupied
0
2
Space
Temperature
SpcTp
AI:72
Current value
of the space
temperature
sensor.
Space
Temperature
Offset
SpcTpOst
AV:71
If the Space
Temperature
Sensor is
reading
incorrectly, you
can use this
option to enter
an offset
temperature to
adjust the
Sensor’s
Temperature.
-100
100
Static
Pressure
StaticPr
AI:270
Current Static
Pressure.