Appendix d - vcb-x bacnet parameters, Pt-link ii interface pt-link ii bacnet, Technical guide 33 – Orion System PT-Link II BACnet2 User Manual

Page 33

Advertising
background image

PT-Link II Interface

PT-Link II BACnet

®

Technical Guide

33

Appendix D - VCB-X BACnet Parameters

BACnet Properties for the VCB-X Controller

Parameter

Name

Object

Description

Limits

Alarm

Group 1

AlmGrp1

AI: 104

See Alarm

Group Bits on

page 39.

Alarm

Group 2

AlmGrp2

AI: 105

See Alarm

Group Bits on

page 39.

Alarm

Group 3

AlmGrp3

AI: 106

See Alarm

Group Bits on

page 39.

Alarm Status

AlmSts

AI: 1

Indicates that

there is an

alarm.

0 = Off

1 = On

See Alarm

Group Bits on

page 39.

Application

Software

Version

AppVer

AI: 99

Current version

of the software

in the unit.

Unit Mode

UnitMode

AI:123

See Unit Mode

Bits on page

39.

Building

Pressure

BuildPr

AI:272

Current value

of the building

pressure sensor.

Building

Pressure
Setpoint

RfPrSt

AV:118

Current

Building

Pressure

Setpoint.

-.20

.20

CO

2

CO2

AI:271

Current CO

2

Level.

CO

2

Minimum

Setpoint

CO2MinLv

AV:287

This is the

threshold CO

2

level at which

the Economizer

Min Damper

Position

Setpoint will

begin to be

reset higher.

0

2000

BACnet Properties for the VCB-X Controller

Parameter

Name

Object

Description

Limits

CO

2

Maximum

Setpoint

CO2

MaxLv

AV:288

This is the CO

2

level at which

the Economizer

Min Damper
Position will

be reset to the

Economizer

Max Position
in High CO

2

.

In between the

Min and Max

CO

2

levels the

Economizer

Min Damper

Position will be

proportionally

reset between

the confi gured

Min Damper

Position and the
Max Position in

High CO

2

.

0

2000

Coil

Temperature

CoilTp

AI: 181

Current coil
temperature

reading.

Coil

Temperature

Offset

ColTpOft

AV:284

If the

Coil

Temperature

Sensor is

reading

incorrectly, you

can use this

option to

enter an offset

temperature to

adjust the

Sensor’s

Temperature.

-100

100

High Coil

Temperature

Setpoint

HiClTpSt

AV:296

This is the

highest that the

Coil

Temperature

will be reset to

during Space

Humidity Reset

of the Coil

Suction

Temperature

Setpoint.

Produces a

dew point in

the supply air

approximately

10˚F above this

setpoint.

35

70

Cooling Low
Reset Source

ClLoRt

AV: 326

Low Cool

Reset Source

Setpoint

1

150

Cooling High

Reset Source

ClHiRt

AV: 327

High Cool

Reset Source

Setpoint

1

150

Revised 4/3/13