BACnet Properties for the VCM Controller

Parameter

Name

Object

Description

Limits

Fan Start Up

Delay

FanDly

BI: 25

Status that indicates

the fan is

commanded to run,

but it is in the start

up delay mode.

Fan

Proving

Alarm

PofAlm

BI: 26

Alarm that

indicates a failure

in the fl ow of the

VFD blower.

Heating

Demand

HtDmnd

BI: 29

Status that indicates

a demand for

heating.

Heating

Enabled

HtEnbl

BI: 30

Status that

indicates that

mechanical heating

is enabled.

High

Supply Air

Temperature

Alarm

HiSaAlm

BI: 33

The Supply Air
has risen above

the Hi SAT Cutoff

Setpoint. Heating

stages begin to deac-

tivate and the fan

continues to run.

Low Supply

Air

Temperature

Alarm

LoSaAlm

BI: 37

The Supply Air has

fallen below the Hi

SAT Cutoff Setpoint

and cooling stages

will begin to deacti-
vate. If the unit is in

Economizer, Vent,

or Heating Mode

the Supply Fan will

shut off.

MODGAS

II

Connected

MdHt2Ins

BI: 39

Status that indicates

the MODGAS II

controller is

connected.

Proof of

Flow

Confi gured

PofCfg

BI: 57

Status that indicates

the proof of fl ow

function has been

confi gured.

REHEAT II

Connected

Rt2Ins

BI: 58

Status that indicates

the MHGRV con-

trollers is connected

to the system.

Warm Up

Mode

Active

WmupD-

mnd

BI: 90

Status that indicates

the control is in the

Warm-up mode.

Mechanical

Cooling

Alarm

MchClAlm

BI: 94

Compressor Relays

are enabled but

the Supply Air

Temperature has

not fallen 5°F w/in

a user-adjustable

time period. This

does not indicate

compressors are

active and will not

shut the unit down.

BACnet Properties for the VCM Controller

Parameter

Name

Object

Description

Limits

Mechanical

Heating

Alarm

MchHtAlm

BI: 95

Heating Mode has

been initiated but

the Supply Air

Temperature has

not risen 5°F w/in

a user-adjustable

time period. This

does not indicate

heat stages are

active and will not

shut the unit down.

Dirty Filter

Detected

DrtFlAlm

BI: 96

Alarm that indicates

the fi lters are dirty.

Control

Temperature
Cool Failure

CtrlTpCF

BI: 108

This alarm is

activated if the

control temperature

does not get within

5°F to the occupied

cooling setpoint

in an hour in the

cooling mode. This

alarm is not used

in 100% outside air

units or supply air

control.

Control

Temperature

Heat Failure

CtrlTpHF

BI: 109

This alarm is

activated if the

control temperature

does not get within

5°F to the occupied

heating setpoint

in an hour in the

heating mode. This

alarm is not used

in 100% outside air

units or supply air

control.

Dehu-

midifi cation

Demand

DehmDmnd

BI: 113

Status that indicates

a demand for

dehumidifi cation.

Outdoor Air

Temperature

Lost

OaTpAlm

BI: 117

Alarm that

indicates a failure

in the outdoor air

temperature.

Smoke

Detected

Alarm

SmokeAlm

BI: 119

Alarm that indicates

the Smoke sensor

has been activated.

Space

Temperature

Sensor Lost

SpcTpAlm

BI: 101

Alarm that indicates

a failure in the

space temperature

sensor.

On Board

Relay 1

OnRly1

BI: 127

Current status of

relay 1.

On Board

Relay 2

OnRly2

BI: 128

Current status of

relay 2.

On Board

Relay 3

OnRly3

BI: 129

Current status of

relay 3.

On Board

Relay 4

OnRly4

BI: 130

Current status of

relay 4.

Appendix H - VCM BACnet Parameters