Pt-link ii bacnet, Technical guide pt-link ii interface 40 – Orion System PT-Link II BACnet2 User Manual

Page 40

Advertising
background image

PT-Link II BACnet

®

Technical Guide

PT-Link II Interface

40

Appendix E - VCM-X Modular & WSHP & RNE BACnet Parameters

BACnet Properties for VCM-X Modular

Parameter

Name

Object

Description

Limits

Modulating

Compressor 2

MdCmp2

AI: 206

Current position
of the 2nd Stage

of Compressor

Modulation.

Head

Pressure 1

HdPr1

AI: 207

Head Pressure for

1st Compressor

Head

Pressure 2

HdPr2

AI: 208

Head Pressure for

2nd Compressor

Condenser

Fan 1

CdFan1

AI: 209

Condenser Fan 1

Signal Status

Condenser

Fan 2

CdFan2

AI: 210

Condenser Fan 2

Signal Status

Remote VFD

Reset

RmVFDPos

AV: 258

Remote VFD

Position Reset

-1

100

BACnet Properties for VCM-X WSHP (Tulsa)

and RNE Controllers

Parameter

Name

Object

Description

Limits

Modulating

Compressor 2

MdCmp2

AI: 206

Current position

of the

2nd Stage of

Compressor

Modulation.

Head Pressure 1

HdPr1

AI: 207

Head Pressure

for

1st Compressor

Head Pressure 2

HdPr2

AI: 208

Head Pressure

for

2nd Compressor

Condenser

Fan 1

CdFan1

AI: 209

Condenser Fan 1

Signal Status

Condenser

Fan 2

CdFan2

AI: 210

Condenser Fan 2

Signal Status

Water Temp. A

WaterTpA

AI: 220

Current water

temperature of

refrigerant for

System A.

Water Temp. B

WaterTpB

AI: 221

Current water

temperature of

refrigerant for

System B.

Remote VFD

Reset

RmVFDPos

AV:
258

Remote VFD

Position Reset

-1

100

BACnet Properties for VCM-X WSHP (Tulsa)

and RNE Controllers

Parameter

Name

Object

Description

Limits

Compressor A1

Low Suction

Pressure Alarm

A1LSPAlm

BI: 222

Alarm that

indicates

Suction Pressure

for

Compressor A1

is below the Low

Suction Pressure

Cooling (Heat-

ing) Setpoint.

Compressor A1

Lockout Alarm

A1LktAlm

BI: 223

Alarm that

indicates

Compressor A1

is locked out.

Compressor A2

Low Suction

Pressure Alarm

A2LSPAlm

BI: 224

Alarm that

indicates

Suction Pressure

for

Compressor A2

is below the Low

Suction Pressure

Cooling (Heat-

ing) Setpoint.

Compressor A2

Lockout Alarm

A2LktAlm

BI: 225

Alarm that

indicates

Compressor A2

is locked out.

Compressor B1

Low Suction

Pressure Alarm

B1LSPAlm

BI: 226

Alarm that

indicates

Suction Pressure

for

Compressor B1

is below the Low

Suction Pressure

Cooling (Heat-

ing) Setpoint.

Compressor B1

Lockout Alarm

B1LktAlm

BI: 227

Alarm that

indicates

Compressor B1

is locked out.

Compressor B2

Low Suction

Pressure Alarm

B2LSPAlm

BI: 228

Alarm that

indicates

Suction Pressure

for

Compressor B2

is below the Low

Suction Pressure

Cooling (Heat-

ing) Setpoint.

Compressor 4

Lockout Alarm

B2LktAlm

BI: 229

Alarm that

indicates

Compressor B2

is locked out.

NOTE:

The following points for the VCM-X Modular, VCM-X

WSHP & RNE Controllers are additional points. All
points and property identifi ers in the VCM-X Con-
troller table (pages 42-47) also apply to the VCM-X
Modular, VCM-X WSHP, and RNE Controllers.

Revised 10/11/12