Connection and wiring information, Pt-link ii interface pt-link ii bacnet, Technical guide 5 – Orion System PT-Link II BACnet2 User Manual

Page 5: Figure 2: pt-link ii bacnet, Interface, Wiring, Enter clear esc prev next down up, Minus, Status setpoints schedules configuration alarms, Overrides balance - test

Advertising
background image

PT-Link II Interface

PT-Link II BACnet

®

Technical Guide

5

Connection and Wiring Information

Figure 2: PT-Link II BACnet

®

Interface

Wiring

Modular Service Tool

Mode

Selection

ENTER

CLEAR

ESC

PREV

NEXT

DOWN

UP

6

5

4

DEC

7

0

8

1

3

2

9

MINUS

-

STATUS

SETPOINTS

SCHEDULES

CONFIGURATION

ALARMS

ON

OVERRIDES

BALANCE - TEST

Line Voltage

PT-Link Interface

MS/TP Connection

To

Network

BACnet

®

MS/TP Connection

To

Network

BACnet

®

24 VAC
(10 VA)

Line Voltage

24 VAC
(8 VA)

Line Voltage

24 VAC
(8 VA)

Line Voltage

Controller

Controller

Controller

Controller

24 VAC
(8 VA)

Line Voltage

24 VAC
(8 VA)

SHLD

T

R

Typical Terminal Blocks. All
Wiring To Be T To T, SHLD
(G) To SHLD (G) & R To R

Note: All Programming Of
Controllers Must Be Done
Using The Modular Service
Tool. The Modular System
Manager Should Not Be Used
On A System That Has A PT-
Link Installed.

Caution: The BACnet
Communication Terminal Block
Must Be Disconnected Before
Connecting The Modular Service
Tool. After Programming The
Controller(s), Disconnect The
Service Tool and Then Reconnect
The Communication Terminal

®

Wiring Notes:
1.) All wiring to be in accordance with local and national electrical codes
and specifications.

2.) All communication wiring to be 18 gauge minimum, 2 conductor twisted
pair with shield. Use Belden #82760 or equivalent.

485

DRIVER

COMM

R

SH

T

LOOP

PROTO

LED1

LED2

TIMER

W_DOG

H-BEAT

POWER

MADE IN USA

www.orioncontrols.com

WattMaster Label

#LB102082

Rev. 01A

OE368-23B-BACNET

PT-LINK II PROTOCOL

TRANSLATOR

FOR BACNET

+24

VAC

GND

LOOP

LED 1

LED 2

=RAPID BLINK

=BLINKS QTY

CONTROLLERS

= STEADY BLINK

PROTO

TIMER

WATCH DOG

H-BEAT

=RAPID BLINK

= STEADY BLINK

= ON SOLID

= STEADY BLINK

LED BLINK CODES (NORMAL)

P

ROTO

C

E

SSO

R

Protocol

Copr

o

c

e

s

s

o

r

w

w

w

.p

ro

to

c

e

ssor.com

1

2

3

4

5

6

7

8

O

N

O

N

1

2

3

4

ON

RX

TX

RSGND

Up To 4 Controllers

Can Be Interconnected.

Controller’s Address

Cannot Be Higher Than 16.

IMPORTANT WIRING NOTE:

Use the Daisy-Chain Topology As Shown in This Diagram.
DO NOT Use a Star Topology with Multiple Units Tied
Directly to the PT-Link II.

Revised 8/31/11