Appendix D - VCB-X BACnet Parameters

BACnet Properties for the VCB-X Controller

Parameter

Name

Object

Description

Limits

Head

Pressure

Setpoint in

Cooling Mode

ClHdPrSt

AV:293

This is the

Head Pressure

Setpoint the

unit will control

to in the

Cooling Mode.

240

PSI

420

PSI

Head

Pressure
Setpoint

in Reheat

Mode

HtHdPrSt

AV:294

This is the

Head Pressure

Setpoint the

unit will control

to in the De-

humidifi cation

Reheat Mode.

240

PSI

420

PSI

Heating Low
Reset Source

HtLoRt

AV: 328

Low Heat Reset

Source Setpoint

1

150

Heating High

Reset Source

HtHiRt

AV: 329

High Heat

Reset Source

Setpoint

1

150

Heating

Enabled

HtEnbl

AI: 30

Status that

indicates that

mechanical

heating is

enabled.

Heating

Setpoint

Mirror

HtSt

AI: 31

Occupied

Heating Mode

Enable Setpoint

Mirror.

Indoor

Humidity

InRh

AI: 67

Current value

of the indoor

humidity

sensor.

Indoor

Humidity

Setpoint

InRhSt

AV:289

If Coil Temp

Reset is being

used this is

also the lowest

Space RH value

that

corresponds

to the Hi Coil

Temp Setpoint.

0

100

High Indoor

Humidity

Reset Limit

HiInRh

AV:292

During Coil

Temp Reset,

this is the

highest Space
RH value that

corresponds to

the Low Coil

Temp Setpoint.

0

100

Indoor

Humidity

Setpoint

Mirror

InRhStM

AI: 114

Mirror of the
InRhSt “read

only.”

Leaving Water

Temperature

LvWtrTp

AI:278

Leaving Water

Temperature

Value

BACnet Properties for the VCB-X Controller

Parameter

Name

Object

Description

Limits

Low

Ambient

Relay

Setpoint

LWAmbnt

AV:285

Temperature at
which the Low

Ambient Relay

will activate in

the Occupied

or Unoccupied

Mode.

-30

70

Modulating

Cooling
Position

MdClPos

AI: 115

Current

position of the

modulating

cooling signal

(Chilled water

or digital

compressor).

Modulating

Gas Valve

Position

MdGs

VPos

AI:274

Current

position of
MODGAS

modulating gas

valve control.

Modulating

Heating

Position

MdHtPos

AI: 116

Current

position of the

modulating

heating signal

(hot water or

SCR heat).

Morning

Warm-Up

Setpoint

WmupTg

AV:281

In a VAV

application,

upon entering

the

occupied mode,

the Warm-up
Demand will

be activated if

the return air

temperature

falls one degree

below this

setpoint.

50

90

Occupied

Cooling

Setpoint

OcpClSt

AV: 42

If the control

temperature

rises one degree

above this

setpoint, the

control will ac-

tivate the cool-

ing demand. If

the control

temperature is

the Supply Air

Sensor, then the
cooling demand

is always

active.

1

110

Revised 4/3/13