WattMaster WCC II User Manual

Page 132

Advertising
background image

Section 3: Screen Descriptions

WCC II Operator’s Guide

Operator Interfaces

3-100

II to report an “SOS” alarm if it has received 10 “Satellite Failure”
messages in a row.

If the user does not specify a number in this section, the ECC/
WCC II will report an “SOS” alarm after one “Satellite Failure”
message. We have found that our method of determining whether a
satellite is still communicating is too sensitive, and we recommend
a number between 5 and 10 for most systems if problems of this
type are encountered.

Disable Energy Consumption print out: NO

If the system is using one or more of the 10 Energy Consumption
Screens
, the accumulated data will automatically be printed once
an hour. If you do not want the ECC/WCC II to print this energy
consumption report each hour, enter a “NO” in this section. Pressing
the

<space bar>

will change the value from YES to NO. Pressing

<Enter>

when the desired value is displayed will enter that choice.

“YES” is assumed by the system unless instructed otherwise.

Clear disk-write-error fl ag: NO

If the ECC/WCC II cannot write a fi le to disk because there is
not enough space left on the disk, a “disk-write-error” message
will appear on the Main Menu Screen. To clear the message, select
“Yes” as the choice for this fi eld.

Time delay for screen blank: 5 minutes

If the system does not detect any keyboard activity for this amount
of time, the screen will go blank. The screen is restored by pressing
the

<space bar>

.

Advertising