Chapter Three

Configuration

Man_455U-D Rev 3.04

Page 57

repeaters don’t clash with responses from the directly communicating device (address
15). This command sets the repeater to 200 msec hold-off.

Slave Repeater station address 21

AT&M0 - Configure mode 0 – Unacknowledged mode.

AT&L1 – Go directly online at start-up

AT&21 - Set Modem’s address to 21

AT&Z0=14,1 - Set all data to go through address 14 to master station, address 1.

AT&R3, AT&H2 - Set Broadcast Repeater mode – Repeat wildcard messages on their
second hop and send these messages out the serial port.

ATS17=4 – Set the receive hold-off. This ensures that the repeated messages from the
repeaters don’t clash with responses from the directly communicating device (address
15). This command sets the repeater to 200 msec hold-off.

Slave devices Site address 36

AT&M0 - Configure mode 0 – Unacknowledged mode.

AT&U36 - Set Modem’s address to 36

AT&Z0=21,14,1 - Set all messages to go to master station, address 1 via repeaters 21
and 14..

AT&R2, AT&H3 – Send wildcard messages on their third hop out the serial port.

3.14 Switch

Configuration

Factory default configuration may be restored to the modem by setting the
DIL switch on the end plate to “Default” setting. This will not change the
configuration settings in non-volatile memory, but will set the volatile
configuration to factory default settings. This is equivalent to entering the
command “AT&F” to the modem. To restore Factory defaults, perform the
following

1.

Set the switch to “Default” (down) position

2.

Turn off module power

3.

Turn module power back on

4.

Return the switch to the up position

The module will now be configured for 19,200 baud communication on the RS232 DB9 port.