You can additionally earth the inverter enclosure if a second earthing or equipotential bonding is
required locally. This prevents touch current if the original protective conductor fails.
Cable requirement:

☐ Earthing cable cross-section: 16 mm² at maximum

1. Strip the earthing cable insulation.

6.3.3

Additional Earthing of the Enclosure

2. Lead the clamping bracket over the earthing

cable. Position the protective conductor on the
left-hand side.

3. Screw the clamping bracket tight using the

M6x16 cheese-head screw and a conical spring
washer (torque: 6 Nm). The teeth of the conical
spring washer must face the clamping bracket.