10 Troubleshooting

CAN

Internal communication fault
Corrective measures:

• If this message is displayed frequently, contact the

SMA Service Line.

Check L-N-PE

L and N are swapped on the AC connection or PE is not connected.
Corrective measures:

• Ensure that the AC cable is correctly connected (see section

6.3.2 "Connecting the Inverter to the Electricity Grid", page 35).

• If the AC cable is connected correctly and this message is still

displayed, contact the SMA Service Line.

Check Varistor

At least one of the varistors is defective.
Corrective measures:

• Check the function of the varistors (see section 10.8).

DC fuse

At least one of the string fuses has tripped or is defective.
Corrective measures:

• Check the function of the string fuses (see section 10.10).

Derating

The inverter reduces its power output due to overheating.
Corrective measures:

• Clean the fans .

The inverter reduces its power output because the DC input current
exceeds the maximum input current of the inverter.
Corrective measures:

• Ensure that the PV plant is designed correctly.

dI-Bfr
dI-Srr

The inverter has detected a change in the differential current.
A change in the differential current can be caused by an earth fault,
residual current or a malfunction. The inverter disconnects from the
electricity grid.
Corrective measures:

• If none of the above causes apply and this message is still

displayed, ensure that the PV plant is insulated correctly and that
there is no earth fault.

dl-Mess

Deviation in the differential current measurement
If this message is displayed frequently, permanent shutdown will be
triggered.
Corrective measures:

• Contact the SMA Service Line.

Message

Cause and corrective measures