10 Troubleshooting

Proceed as follows to check each string in the PV plant for earth faults.

1. Disconnect the inverter from all voltage sources (see section 9).
2. Measure the voltages:

• Measure the voltages between the positive pole and the earth potential (PE).
• Measure the voltages between the negative pole and the earth potential (protective

conductor).

• Measure the voltages between the positive and negative pole.

If the following results are present at the same time, there is an earth fault in the PV plant.

– All measured voltages are stable.
– The sum of the two voltages against the earth potential is approximately equal to the voltage

between the positive and negative poles.

• Determine the location of the earth fault via the ratio of the two measured voltages.
• Eliminate the earth fault.

If there is no earth fault and the message is still displayed, contact the SMA Service Line.

Example: Location of the earth fault
The example shows an earth fault between the second and third PV module.

3. Recommission the inverter (see section 8 "Commissioning", page 51).