10 Troubleshooting

SMA Solar Technology AG

Earthfault

The electrical insulation between the PV plant and earth is defective.
The resistance between the positive or negative DC connection and
earth is outside the permissible range.
Corrective measures:

• Ensure that the PV plant is insulated correctly.
• Ensure that there is no earth fault Checking the PV Plant for Earth

Faults.

Riso-Sense

The insulation measurement has failed.
Corrective measures:

• If this message is displayed frequently, contact the

SMA Service Line.

ROM

The inverter firmware is faulty.
Corrective measures:

• If this message is displayed frequently, contact the

SMA Service Line.

SD-DI converter

The inverter has detected an insulation fault on the DC side.
Corrective measures:

• Ensure that the PV plant is insulated correctly.
• Ensure that there is no earth fault Checking the PV Plant for Earth

Faults.

SD-Imax

The inverter has detected an overcurrent on the AC side. The inverter
disconnects from the electricity grid for safety reasons and afterwards
tries to reconnect to the grid.
Corrective measures:

• If this message is displayed frequently, contact the

SMA Service Line.

SD-WR-Bruecke

The inverter has detected a fault in the power electronics. The inverter
disconnects from the electricity grid for safety reasons and afterwards
tries to reconnect to the grid.
Corrective measures:

• If this message is displayed frequently, contact the

SMA Service Line.

Shutdown

Temporary inverter fault
Corrective measures:

• Contact the SMA Service Line.

Message

Cause and corrective measures