10 Troubleshooting

Status messages are shown in the second line of the display and always start with the word “Mode”.
Status messages indicate operating states which do not represent errors or faults. The inverter

continues feeding into the electricity grid.

10.2.2 Status Messages

Message

Explanation

Balanced

The inverter has disconnected from the electricity grid or is limiting its
power over a ten-minute average to 4.6 kVA. The inverter is part of a
three-phase system with two further inverters and is equipped with the
SMA Power Balancer to prevent the formation of unbalanced loads.

Derating

This message can have several causes:

• Overtemperature in the inverter. The inverter reduces its power

to prevent overheating.

• External active power limitation via the Power Reducer Box and

Sunny WebBox. The inverter reduces its power output
automatically due to the network operator's specifications. The
Power Reducer Box transfers the signal from the network
operator to the inverter via the Sunny WebBox.

disturbance

The inverter has detected a fault. The specific message is also
displayed (see section 10.2.3 "Errors, Faults, Warnings", page 60).

Earthfault

Measurement of the insulation resistance of the PV plant

Error

The inverter has detected an error. The specific error message is also
displayed (see section 10.2.3 "Errors, Faults, Warnings", page 60).

grid mon.

Grid monitoring. This message appears before the inverter is
connected to the electricity grid if irradiation is low and following an
error.

MPP

The inverter is operating in MPP mode. MPP is the standard display
message when operating under normal irradiation conditions.

MPP-Peak

The inverter is operating in MPP mode above its nominal power.

MPP-Search

The inverter is calculating the MPP.

offset

Offset alignment of the measurement electronics

Stop

Operation interrupted

V-Const

Constant voltage mode

Waiting

The conditions for grid connection are not (yet) fulfilled.