Manufacturer specific profile objects (ds 301) – Yaskawa 1000 Series Drive Option - CANopen Technical Manual User Manual

Page 20

Advertising
background image

8 Object Dictionary

20

YASKAWA ELECTRIC

SIEP C730600 45B 1000-Series Option SI-S3 Technical Manual

1016 (Hex) - Consumer Heartbeat Time

This object defines the Consumer heartbeat time. It must be set to a higher value than the producer heartbeat time set in the master. When set to 0,

consumer heartbeat is disabled.

1017 (Hex) - Producer Heartbeat Time

This object determines the cycle time the CANopen Option uses to produce a heartbeat signal. When set to 0, the SI-S3 does not produce a heartbeat

signal.

1018 (Hex) - Identity Object

This object contains general information about the drive.

Manufacturer Specific Profile Objects (DS 301)

The SI-S3 option card offers the manufacturer specific objects listed below.

These objects are specific to Yaskawa products and therefore not available on other CANopen products.
The manufacturer-specific object list consists of objects that have predefined, non-changeable content and objects that are freely configurable. The

content of freely configurable objects can be determined by linking these objects to drive parameters, monitors or MEMOBUS/Modbus registers

(refer to

Selectable Object Content on page 27

).

Input objects are processed in a cycle of 2 ms. Output objects are, depending on the object, updated in a cycle of either 2 ms or 8 ms. The update

cycle cannot be changed.
Some of the output objects support a Change of State filter that can be used to reduce the bus traffic when quickly-changing values such as the

output current and motor speed are mapped to TxPDOs with Change of State (transmission type FE (Hex)) enabled. Refer to

Change of State Filter

on page 29

and

Transmission Type FE (Hex) for Transmit PDOs on page 29

for details.

Note: Freely configurable object content and the object Change of State filter function are available in option card software version 3102 and later.

2000 (Hex) - Operation Command

This object is used to start and stop the drive, to control the multi-function digital input terminals, and to trigger and reset faults.

2010 (Hex) - Speed Reference/Speed Limit

Sets the speed reference or speed limit. The unit of this value depends on the setting of the drive parameter o1-03.

The value will be used as the speed reference for speed control (d5-01 = 0) or as the speed limit in torque control (d5-01 = 1).

Note: The availability of the torque control function depends on the drive and the selected control mode. For details, refer to the technical manual for the drive.

Index (Hex)

Subindex

Content

Access

PDO Mapping

Value Range

Units

1016

1

Consumer heartbeat time

Read / Write

No

Unsigned 32

1 ms

Index (Hex)

Subindex

Content

Access

PDO Mapping

Value Range

Units

1017

Producer heartbeat time

Read / Write

No

Unsigned 16

1 ms

Index (Hex)

Subindex

Content

Access

PDO Mapping

Value Range

1018

1

Identity object

Read Only

No

Unsigned 32

Index (Hex)

Subindex

Content

Access

PDO Mapping

Data Length

2000

0

Operation Command

Read / Write

Possible

2 byte

Bit No. (Hex)

Description

Function

0

Forward Run

1: Forward run, 0: Stop (Enabled when b1-02=3)

1

Reverse Run

1: Reverse run, 0: Stop (Enabled when b1-02=3)

2

Terminal S3 Function

Multi-Function Input: H1-03

3

Terminal S4 Function

Multi-Function Input: H1-04

4

Terminal S5 Function

Multi-Function Input: H1-05

5

Terminal S6 Function

Multi-Function Input: H1-06

6

Terminal S7 Function

Multi-Function Input: H1-07

7

Terminal S8 Function

Multi-Function Input: H1-08

8

External Fault (EF0)

1: External Fault Input (EF0)

9

Fault Reset

1: Fault Reset

A to F

Not used

Index (Hex)

Subindex

Content

Access

PDO Mapping

Data Length

2010

0

Speed command

Read / Write

Possible

2 byte

Advertising