10 Process Data Objects (PDO)

YASKAWA ELECTRIC SIEP C730600 45B 1000-Series Option SI-S3 Technical Manual

29

Receive PDO Configuration and Mapping

A receive PDO can be configured using the corresponding 14†† (Hex) object, and the mapping can be changed in the 16†† (Hex) object that

belongs to the PDO.

PDO Configuration

PDO Mapping

Note: When changing the PDO mapping, always first set subindex 0 to “0”, then set subindex 1 to subindex n. Then activate the mapping by setting subindex 0 to the number

of mapped objects n.

Transmit PDO Configuration and Mapping

A transmit PDO can be configured by using the corresponding 18†† (Hex) object, and the mapping can be changed in the 1A†† (Hex) object

that belongs to the PDO.

PDO Configuration

PDO Mapping

Note: When changing the PDO mapping, always first set subindex 0 to “0”, then set subindex 1 to subindex n. Then activate the mapping by setting subindex 0 to the number

of mapped objects n.

Transmission Type FE (Hex) for Transmit PDOs

When the transmission type of a TxPDO is set to FE (Hex), the PDO is automatically transmitted whenever the value in one of the mapped objects

changes.
When this transmission type is used for a TxPDO that is mapped to an object with a Change of State filter, the filter can be used to reduce the

amount of data transferred if the object value changes quickly (refer to

Change of State Filter on page 29

). The filter must be set to a value that is

different from FFFF (Hex). If a large filter value is applied, then it can be helpful to also set an event timer for the PDO (18†† (Hex), subindex 5).

In this way, the PDO is triggered cyclically even if the change in the value of the linked object does not exceed the filter value. In this way,

variations within the filter can still be seen without having a large number of messages sent.

Note: When a Change of State filter and an event timer are used simultaneously, the PDO will be triggered by whichever one is received first, the timer event or the Change of

State event. If the PDO is triggered by the Change of State event, the event timer will be reset.

Change of State Filter

Note: This function is available in option card software 3102 and later.

Some Output objects of the Manufacturer Specific Profile support a Change of State filter. If such an object is mapped to a TxPDOs with

transmission type FE (Change of State), and the filter is set up, a Change of State event is triggered (i.e., the PDO is transmitted) only if the change

in the object value exceeds the filter value. Such objects have the following structure and can be set up as explained below.

Subindex 0: Number of Entries

Contains the number of subindices.

Subindex 1: Object Value

This subindex contains the value of the object (value of the MEMOBUS/Modbus register specified in the subindex 2).

Index (Hex)

Subindex

Content

Default

Access

Data Length

14††

0

Largest subindex supported

2

Read Only

1 byte

1

COB-ID used by the RxPDO

see Receive PDO table above

Read/Write

4 byte

2

Transmission type

FE

Read/Write

1 byte

Index (Hex)

Subindex (Hex)

Content

Default

Access

Data Length

16††

0

Number of mapped RxPDO’s

see Receive PDO table above

Read/Write

1 byte

1 to 40

Data length, subindex and index of the object to be mapped

see Receive PDO table above

Read/Write

4 byte

Index (Hex)

Subindex

Content

Default

Access

Data Length

18††

0

Largest subindex supported

5

Read Only

1 byte

1

COB-ID used by the TxPDO

see TxPDO table above

Read/Write

4 byte

2

Transmission type

depends on PDO

Read/Write

1 byte

3

Inhibit time (Set as a multiple of 100 us)

0

Read/Write

2 byte

5

Event timer (Set as a multiple of 1 ms)

0

Read/Write

2 byte

Index (Hex)

Subindex (Hex)

Content

Default

Access

Data Length

1A††

0

Number of mapped PDOs

see transmit PDO table above

Read Only

1 byte

1 to 40

Data length, subindex and index of the object to be mapped

see transmit PDO table above

Read/Write

4 byte

Index (Hex)

<1> Read / Write access when SI-S3 is in the Pre-Operational state, Read only access if the SI-S3 is in the Operational state or if the drive is running.

Subindex

Content

Access

PDO Mapping

Data Length

2101, 2111, 2121,

2131, 2180 to 21E0,

2201

0

Number of entries

Read Only

No

1 byte

1

Object value

Read Only

Possible

2 byte

2

MEMOBUS/Modbus register address for content

Read / Write

<1>

No

2 byte

3

Filter value

Read / Write

<1>

No

2 byte

4

Filter type

Read / Write

<1>

No

2 byte