8 object dictionary – Yaskawa 1000 Series Drive Option - CANopen Technical Manual User Manual

Page 25

Advertising
background image

8 Object Dictionary

YASKAWA ELECTRIC SIEP C730600 45B 1000-Series Option SI-S3 Technical Manual

25

6041 (Hex) - Statusword

This object shows different states of the device.

6042 (Hex) - vl Target Velocity

This object sets the speed reference and the run command. It is internally multiplied with the vl dimension factor (604C). Can be set when the status

in Controlword 6040 (Hex) is “Operation Enable”.

6043 (Hex) - vl Velocity Demand

The vl velocity effort is the output frequency of the drive to the motor.

6044 (Hex) - vl Control Effort

The v1 control effort is the motor speed.

6046 (Hex) - vl Velocity Min Max Amount

This object provides two subindexes to set the minimum and maximum speed reference in r/min.

6048 (Hex) - vl Velocity Acceleration

The vl velocity acceleration specifies the acceleration time. The quotient of the subindexes delta speed and delta time determines the acceleration

time. The object values correspond to the acceleration time setting in the drive.

6049 (Hex) - vl Velocity Deceleration

The vl velocity min max amount specifies the deceleration time. The quotient of the subindexes delta speed and delta time determines the

deceleration time. The object values correspond to the deceleration time setting in the drive.

604A (Hex) - vl Velocity Quick Stop

The vl velocity quick stop specifies the quick stop ramp. The quotient of the subindexes delta speed and delta time determines the quick stop ramp

time. The object values correspond to the fast stop time setting in the drive.

604C (Hex) - vl Dimension Factor

The vl dimension factor is multiplied with the target velocity. The quotient of the subindexes vl dimension factor numerator and vl dimension factor

denominator determines the vl dimension factor.

Index (Hex)

Subindex

Content

Access

PDO Mapping

Value Range

6041

0

Statusword

Read Only

Possible

0...65535

Index (Hex)

Subindex

Content

Access

PDO Mapping

Value Range

Unit

6042

0

vl target velocity

Read / Write

Possible

-32768...0...32767

r/min

Index (Hex)

Subindex

Content

Access

PDO Mapping

Value Range

Unit

6043

0

vl velocity demand

Read Only

Possible

-32768...0...32767

r/min

Index (Hex)

Subindex

Content

Access

PDO Mapping

Value Range

Unit

6044

0

vl control effort

Read Only

Possible

-32768...0...32767

r/min

Index (Hex)

Subindex

Content

Access

PDO Mapping

Value Range

Unit

6046

1

vl velocity min amount

Read / Write

Possible

0...(2

32

-1)

r/min

2

vl velocity max amount

Index (Hex)

Subindex

Content

Access

PDO Mapping

Value Range

Unit

6048

1

Delta speed

Read / Write

Possible

0...(2

23

-1)

r/min

2

Delta time

0...65535

sec

Index (Hex)

Subindex

Content

Access

PDO Mapping

Value Range

Unit

6049

1

Delta speed

Read / Write

Possible

0...(2

23

-1)

r/min

2

Delta time

0...65535

sec

Index (Hex)

Subindex

Content

Access

PDO Mapping

Value Range

Unit

604A

1

Delta speed

Read / Write

Possible

0...(2

23

-1)

r/min

2

Delta time

0...65535

sec

Index (Hex)

Subindex

Content

Access

PDO Mapping

Value Range

604C

1

vl dimension factor numerator

Read / Write

Possible

-2

31

...(2

31

-1)

2

vl dimension factor denominator

Advertising