8 Object Dictionary

24

YASKAWA ELECTRIC

SIEP C730600 45B 1000-Series Option SI-S3 Technical Manual

2180 (Hex) to 21F0 (Hex) - Freely Configurable Output Objects

Note: These objects are available in option card software version 3102 and later.

The content of these objects can be freely selected by linking them to drive MEMOBUS/Modbus registers. For 2 byte objects a Change of State

filter can be applied. Refer to

Change of State Filter on page 29

for details.

2200 (Hex) / 2201 (Hex) - Motor Speed

These objects can be used to monitor the motor speed. The value in object 2200 (Hex) is not filtered. For the value in object 2201 (Hex), a Change

of State filter can be set up as explained in

Change of State Filter on page 29

.

The availability of the object content depends on the drive control mode. If the selected control mode does not support this monitor (equal to drive

monitor U1-05), the object value will be 0. Refer to the drive technical manual for details.

Drives and Motion Profile Objects (DSP 402)

The drive supports Drive and Motion Profile DSP 402 Velocity Mode. Before using Velocity Mode, objects for following parameters must be set up

in the drive:

• The number of motor poles must be set to E2-04.

• The frequency reference and output frequency display unit must be set to r/min by setting parameter o1-03 = 2.

If these settings are incorrect, the Velocity Mode objects may be unusable, or the drive might not operate as expected.

Note: Drive and Motion Control (DSP 402) cannot be set or referenced unless o1-03 = 2.

6040 (Hex) - Controlword

This object sets the device to different states.

Index (Hex)

<1> Read / Write access when SI-S3 is in the Pre-Operational state, Read only access if the SI-S3 is in the Operational state or if the drive is running.

Subindex

Content

Default

Access

PDO Mapping Data Length Update Cycle

2180

0

Number of entries

4

Read Only

No

1 byte

-

1

Value

Input Terminal Status

Read Only

Possible

2 byte

8 ms

2

MEMOBUS/Modbus register address for content

0049 (Hex)

Read / Write

<1>

No

2 byte

-

3

Filter value

0

Read / Write

<1>

No

2 byte

4

Value filter type

1 (Bitmask)

Read / Write

<1>

No

2 byte

2190

0

Number of Entries

4

Read Only

No

1 byte

-

1

Value

Analog Input A1 Monitor

Read Only

Possible

2 byte

8 ms

2

MEMOBUS/Modbus register address for content

004E (Hex)

Read / Write

<1>

No

2 byte

-

3

Filter value

FFFF (Hex)

Read / Write

<1>

No

2 byte

4

Value filter type

0 (Analog)

Read / Write

<1>

No

2 byte

21A0

0

Number of entries

4

Read Only

No

1 byte

-

1

Value

-

Read Only

Possible

2 byte

8 ms

2

MEMOBUS/Modbus register address for content

FFFF (Hex)

Read / Write

<1>

No

2 byte

-

3

Filter value

FFFF (Hex)

Read / Write

<1>

No

2 byte

4

Value filter type

0 (Analog)

Read / Write

<1>

No

2 byte

21B0 to 21E0

0

Number of entries

4

Read Only

No

1 byte

-

1

Value

-

Read Only

Possible

2 byte

2 ms

2

MEMOBUS/Modbus register address for content

FFFF (Hex)

Read / Write

<1>

No

2 byte

-

3

Filter value

FFFF (Hex)

Read / Write

<1>

No

2 byte

4

Value filter type

0 (Analog)

Read / Write

<1>

No

2byte

21F0

0

Number of entries

2

Read Only

No

1 byte

-

1

Value

-

Read Only

Possible

4 byte

8 ms

2

MEMOBUS/Modbus register address for content 1 and 2 FFFF (Hex)/FFFF (Hex) Read / Write

<1>

No

4 byte

-

Index (Hex)

<1> Available in option card software version 3102 and later.

<2> Read / Write access when SI-S3 is in the Pre-Operational state, Read only access if the SI-S3 is in the Operational state or if the drive is running.

Subindex

Content

Default

Access

PDO Mapping Data Length Update Cycle

2200

0

Motor Speed

-

Read Only

Possible

2 byte

2 ms

2201

<1>

0

Number of Entries

4

Read Only

No

1 byte

-

1

Motor Speed

-

Read Only

Possible

2 byte

2 ms

2

MEMOBUS/Modbus register address for content

0044 (Hex)

Read Only

No

2 byte

-

3

Filter value

FFFF (Hex)

Read / Write

<2>

No

2 byte

4

Value filter type

0 (Analog)

Read / Write

<2>

No

2 byte

Index (Hex)

Subindex

Content

Access

PDO Mapping

Value Range

6040

0

Controlword

Read / Write

Possible

0...65535