8 Object Dictionary

26

YASKAWA ELECTRIC

SIEP C730600 45B 1000-Series Option SI-S3 Technical Manual

604D (Hex) - vl Pole Number

The vl pole number sets the number of motor poles and is used to calculate all speed related values in r/min. This value corresponds to the number

of motor poles setting in the drive.

6061 (Hex) - Modes of Operation Display

This object shows the mode of the device. The object supports 2 (Velocity Mode) only.

60FD (Hex) - Digital Inputs

This object contains the drive digital output status (seen as input to the network).
The content of this object is equal to drive MEMOBUS/Modbus register 004A (Hex) (drive output terminal status monitor U1-11), and depends on

the drive the SI-S3 option card is used with. For details of the contents of this register refer to the technical manual for the drive.

60FE (Hex) - Digital Outputs

This object is used to set drive digital inputs (seen as output from the network).

Index (Hex)

Subindex

Content

Access

PDO Mapping

Value Range

604D

0

vl pole number

Read / Write

No

0...255

Index (Hex)

Subindex

Content

Access

PDO Mapping

Value Range

6061

0

Modes of operation display

Read Only

Possible

-128...127

Index (Hex)

Subindex

Content

Access

PDO Mapping

Value Range

60FD

0

Drive digital input status

Read Only

Possible

0...(2

32

-1)

Bit No. (Hex)

Function

Description

0 to F

Reserved

10 to 1F

Bit 0 to F of drive register 004A (Hex) (drive output terminal status monitor U1-11)

1: ON 0: OFF

Index (Hex)

Subindex

Content

Access

PDO Mapping

Value Range

60FE

1

Drive Digital Input Command

Read / Write

Possible

0...(2

32

-1)

Bit No. (Hex)

Function

Description

0 to 11

Not used

12

Terminal S3 Function

Multi-Function Input: H1-03

13

Terminal S4 Function

Multi-Function Input: H1-04

14

Terminal S5 Function

Multi-Function Input: H1-05

15

Terminal S6 Function

Multi-Function Input: H1-06

16

Terminal S7 Function

Multi-Function Input: H1-07

17

Terminal S8 Function

Multi-Function Input: H1-08

18

External Fault (EF0)

1: External Fault Input (EF0)

19

Fault Reset

1: Fault Reset

1A to 1F

Not used

Advertising