8 Object Dictionary

YASKAWA ELECTRIC SIEP C730600 45B 1000-Series Option SI-S3 Technical Manual

23

2120 (Hex) / 2121 (Hex) - Output Current

These objects can be used to monitor the drive output current in amperes. The current value resolution is the same as in drive monitor U1-03 (For

details, refer to the Technical Manual for the drive). The value in object 2120 (Hex) is not filtered. For the value in object 2121 (Hex), a Change of

State filter can be set up as explained in

Change of State Filter on page 29

.

2130 (Hex) / 2131 (Hex) - Output Torque Reference

These objects can be used to monitor the output torque reference. The value in object 2130 (Hex) is not filtered. For the value in object 2131 (Hex),

a Change of State filter can be set up as explained in

Change of State Filter on page 29

.

The availability of this object content depends on the drive control mode. If the selected control mode does not support this monitor (equal to drive

monitor U1-09), the torque reference monitor value will be 0. Refer to the drive technical manual for details.

2140 (Hex) - MEMOBUS/Modbus Read Response

This object contains the data of the drive MEMOBUS/Modbus register specified in object 2040 (Hex). Bytes 1 and 2 of subindex 1 will contain the

data, and bytes 3 and 4 will contain the MEMOBUS/Modbus Address that was read.

2150 (Hex) - MEMOBUS/Modbus Write Response

This object contains the response from the drive when writing a drive parameter with a MEMOBUS/Modbus write command (object 2050 (Hex)).

Bytes 1 and 2 of subindex 1 will contain the data that was written, and bytes 3 and 4 will contain the MEMOBUS/Modbus Address that was written

to.

2155 (Hex) - PDO Parameter Write Response

Note: Available in option card software version 3102 and later.

This object contains the response from the drive when writing a drive parameter directly using a RxPDO. Byte 1 contains the lower byte and byte 2

contains the higher byte of the message identifier (COB-ID) for the message that contains the parameter write request. Byte 3 contains the number

of errors. This object can only be read if the SI-S3 option is in the Operational state.
Refer to

Accessing Drive Parameters, Monitors and Control Registers Using PDOs on page 31

for details on writing parameters using PDOs.

2160 (Hex) - MEMOBUS/Modbus Not Limited Enter Command Response

This object contains the response from the drive when writing an Enter command using object 2060 (Hex).

Index (Hex)

<1> Available in option card software version 3102 and later.

<2> Read / Write access when SI-S3 is in Pre-Operational state, Read only access if the SI-S3 is in the Operational state or if the drive is running.

Subindex

Content

Default

Access

PDO Mapping Data Length Update Cycle

2120

0

Output Current

-

Read Only

Possible

2 byte

8 ms

2121

<1>

0

Number of entries

4

Read Only

No

1 byte

-

1

Output Current

-

Read Only

Possible

2 byte

8 ms

2

MEMOBUS/Modbus register address for content

00FB (Hex)

Read Only

No

2 byte

-

3

Filter value

FFFF (Hex)

Read / Write

<2>

No

2 byte

4

Value filter type

0 (Analog)

Read / Write

<2>

No

2 byte

Index (Hex)

<1> Available in option card software version 3102 and later.

<2> Read / Write access when SI-S3 is in Pre-Operational state, Read only access if the SI-S3 is in the Operational state or if the drive is running.

Subindex

Content

Default

Access

PDO Mapping Data Length Update Cycle

2130

0

Torque Reference

-

Read Only

Possible

2 byte

8 ms

2131

<1>

0

Number of entries

4

Read Only

No

1 byte

-

1

Torque Reference

-

Read Only

Possible

2 byte

8 ms

2

MEMOBUS/Modbus register address for content

0048 (Hex)

Read Only

No

2 byte

-

3

Filter value

FFFF (Hex)

Read / Write

<2>

No

2 byte

4

Value filter type

0 (Analog)

Read / Write

<2>

No

2byte

Index (Hex)

Subindex

Content

Access

PDO Mapping

Data Length

2140

0

Number of entries

Read Only

Possible

1 byte

1

MEMOBUS/Modbus read response

2 + 2 byte

MEMOBUS/Modbus

Data + Address

Index (Hex)

Subindex

Content

Access

PDO Mapping

Data Length

2150

0

Number of entries

Read Only

Possible

1 byte

1

MEMOBUS/Modbus write response

2 + 2 byte

MEMOBUS/Modbus

Data + Address

Index (Hex)

Subindex

Content

Access

PDO Mapping

Data Length

2155

0

PDO Parameter Write Response (COB-ID of the

RxPDO and number of errors)

Read Only

Possible

3 byte

Index (Hex)

Subindex

Content

Access

PDO Mapping

Data Length

2160

0

MEMOBUS/Modbus not limited enter command

response

Read Only

Possible

4 byte