8 Object Dictionary

YASKAWA ELECTRIC SIEP C730600 45B 1000-Series Option SI-S3 Technical Manual

21

2020 (Hex) - Torque Reference/Torque Limit

This object sets the torque reference or the torque limit in units of 0.1%.

To use this object, set drive parameter F6-06 to 1. The value will be used as the torque reference for torque control (d5-01 = 1) or as the torque limit

in speed control (d5-01 = 0).

Note: The availability of the torque control and torque limit function depends on the drive and the selected control mode. For details, refer to the technical manual for the

drive.

2030 (Hex) - Torque Compensation

This object sets the torque compensation in units of 0.1%.

2040 (Hex) - MEMOBUS/Modbus Read Request

This object can be used to read out the content of drive MEMOBUS/Modbus registers. The address of the MEMOBUS/Modbus must be written in

byte 3 and 4 of Subindex 1, bytes 1 and 2 have to be set to 0. After sending a MEMOBUS/Modbus Read Request to the drive, the MEMOBUS/

Modbus register content can be read out from object 2140H.
For more details on MEMOBUS/Modbus address and data, refer to the MEMOBUS/Modbus Data Table in Appendix C of the technical manual for

the drive.

2050 (Hex) - MEMOBUS/Modbus Write Request

Using this object, drive MEMOBUS/Modbus registers can be written. The data must be written in byte 1 and 2 of Subindex 1, and the MEMOBUS/

Modbus address must be written in bytes 3 and 4. After sending a MEMOBUS/Modbus Write Request to the drive, the response can be read from

object 2150H.
For more details on MEMOBUS/Modbus address and data, refer to the MEMOBUS/Modbus Data Table in Appendix C of the technical manual for

the drive.

2060 (Hex) - MEMOBUS/Modbus Unlimited ENTER Command

Depending on the drive parameter H5-11 setting, an ENTER command must be used to activate drive parameters changed via MEMOBUS/Modbus

Write Commands. The unlimited ENTER command activates parameters in the drive RAM only. If the drive power is cycled, parameter changes are

lost. If more than one parameter has been changed, it is enough to send only one ENTER command after the last parameter change. Doing so will

activate all changed parameters. This ENTER command can be used without limitations.
To execute this type of ENTER command, "save" (73H + 61H + 76H + 65H) must be written in object 2060H, subindex 0.

2070 (Hex) - MEMOBUS/Modbus Limited ENTER Command

Depending on the drive parameter H5-11 setting, an ENTER command must be used to activate drive parameters changed via MEMOBUS/Modbus

Write Commands. The limited ENTER command activates parameters in the drive’s RAM and saves them to the EEPROM. When power supply

loss occurs or the power supply is cycled, the drive will operate using the saved parameters. If more than one parameter has been changed, it is

enough to send only one ENTER command after the last parameter change. Doing so will activate all changed parameters. This type of ENTER

command can be applied approximately 100,000 times, and should be used only when necessary.
To execute this type of ENTER command, "save" (73H + 61H + 76H + 65H) must be written in object 2070H, subindex 0.

Index (Hex)

Subindex

Content

Access

PDO Mapping

Data Length

2020

0

Torque Reference / Torque Limit

Read / Write

Possible

2 byte

Index (Hex)

Subindex

Content

Access

PDO Mapping

Data Length

2030

0

Torque Compensation

Read / Write

Possible

2 byte

Index (Hex)

Subindex

Content

Access

PDO Mapping

Data Length

2040

0

Number of entries

Read Only

Possible

1 byte

1

MEMOBUS/Modbus read request

Read / Write

2 + 2 byte

0000H + MEMOBUS/Modbus

Address

Index (Hex.)

Subindex

Content

Access

PDO Mapping

Data Length

2050

0

Number of entries

Read Only

Possible

1 byte

1

MEMOBUS/Modbus Write request

Read / Write

2 + 2 byte

MEMOBUS/Modbus

Data + Address

Index (Hex)

Subindex

Content

Access

PDO Mapping

Data Length

2060

0

Unlimited ENTER command

Read / Write

Possible

4 byte

Index (Hex)

Subindex

Content

Access

PDO Mapping

Data Length

2070

0

Limited enter command

Read / Write

Possible

4 byte