6 mechatrolink option drive parameters, 6mechatrolink option drive parameters – Yaskawa 1000 Series Drive Option - MECHATROLINK-II Technical Manual User Manual

Page 14

Advertising
background image

14

YASKAWA ELECTRIC SIEP C730600 50A YASKAWA AC Drive-Option Card MECHATROLINK-II Technical Manual

6 MECHATROLINK Option Drive Parameters

6

MECHATROLINK Option Drive Parameters

Confirm proper setting of the all parameters in

Table 4

before starting network communications.

Table 4 Parameter Settings

No.

<1> To start and stop the drive with the MECHATROLINK master device using serial communications, set b1-02 to 3. To control the frequency

reference of the drive via the master device, set b1-01 to 3.

<2> If set to 3, then the drive will continue to operate when a fault is detected. Take proper measures such as installing an emergency stop switch.

<3> Power must be cycled in order for any setting changes to take affect.

<4> All station addresses must be unique. If set to 20 or 3F, a Station Address Error (AEr) will occur and the ERR light will turn on.

<5> Setting byte 10 of INV_CTL to 0EH enables the register set by F6-23. Byte 11 and 12 of the response data enable the register content set by

F6-23.

<6> Setting byte 10 of INV_CTL to 0FH enables the register set by F6-24. Byte 11 and 12 of the response data enable the register content set by

F6-24.

Name

Description

Default

b1-01

<1>

Frequency Reference Selection 1

Selects the frequency reference input source
0: Operator - Digital preset speed d1-01 to d1-17
1: Terminals - Analog input terminal A1 or A2
2: MEMOBUS/Modbus communications
3: Option PCB
4: Pulse Input (Terminal RP)

1

b1-02

<1>

Run Command Selection 1

Selects the run command input source
0: Digital Operator - RUN and STOP keys
1: Digital input terminals S1 to S8
2: MEMOBUS/Modbus communications
3: Option PCB

1

F6-01

<2>

Communications Error Operation
Selection

Determines drive response when a bUS error is detected during communications with
the MECHATROLINK-II Option
0: Ramp to Stop. Decelerate to stop using the deceleration time in C1-02.
1: Coast to Stop
2: Fast-Stop. Decelerate to stop using the deceleration time in C1-09.
3: Alarm Only

1

F6-02

External Fault from Comm.
Option Detection Selection

Sets the condition for external fault detection (EF0)
0: Always detected.
1: Detection during run only.

0

F6-03

<2>

External Fault from Comm.
Option Operation Selection

Determines drive response for external fault input (EF0) detection during
MECHATROLINK-II communication
0: Ramp to Stop. Decelerate to stop using the deceleration time in C1-02.
1: Coast to Stop
2: Fast-Stop. Decelerate to stop using the deceleration time in C1-09.
3: Alarm Only

1

F6-07

Multi-Step Speed Enable/Disable
Selection when NetRef/ComRef is
Selected

0: Multi-step speed reference disabled (Same as F7)
1: Multi-step speed reference enabled (Same as V7)

0

F6-08 Reset Communication Parameters

Determines which communication-related parameters are set back to their original
default values when the drive is initialized.
0: Do not reset F6-†† parameters when the drive is initialized using parameter A1-03.
1: Rest F6-†† parameters when the drive is initialized using parameter A1-03.

Note: Setting this parameter does not affect communication-related

parameters.

0

F6-20

<3> <4>

MECHATROLINK Station Address 20 to 3FH

21

F6-21

<3>

MECHATROLINK Frame Size

0: 32 byte
1: 17 byte

0

F6-22

<3>

MECHATROLINK Link Speed

0: 10 Mbps
1: 4 Mbps

0

F6-23

<3> <5>

MECHATROLINK Monitor
Selection (E)

0 to FFFFH

0

F6-24

<3> <6>

MECHATROLINK Monitor
Selection (F)

0 to FFFFH

0

F6-25

Operation Selection at Watchdog
Error (E5)

0: Ramp to stop. Decelerate to stop using the deceleration time in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration time in C1-09.
3: Alarm only.

1

F6-26

MECHATROLINK bUS Errors
Detected

Sets the number of option communication errors (bUS).
2 to 10

2

Advertising