9 troubleshooting, Fault detection processing, 9troubleshooting – Yaskawa 1000 Series Drive Option - MECHATROLINK-II Technical Manual User Manual

Page 30

Advertising
background image

30

YASKAWA ELECTRIC SIEP C730600 50A YASKAWA AC Drive-Option Card MECHATROLINK-II Technical Manual

9 Troubleshooting

9

Troubleshooting

‹

Fault Detection Processing

Faults can be detected by two methods: Drive fault detection and SI-T3 fault detection.

The SI-T3 is notified of drive faults by the internal interface, and the SI-T3 sends the response data, ALARM or
STATUS.

The SI-T3 notifies drive of SI-T3 faults by the internal interface, and the faults are simultaneously sent the response data,
ALARM or STATUS.

The following four types of faults can be detected. The subsequent operation varies depending on the type of fault.

Table 19 Fault Type

Table 20 Fault Type and SI-T3 Processing

Note:The meanings of each symbol are as follows.

− : No change

←: Fault notification from Drive

When consecutive alarms occur, the SI-T3 provides notification of the most recent alarm with a MECHATROLINK
response data. If warnings occur simultaneously, notification priority is given to the warning with the lowest warning
code. If alarms and warnings are mixed together, the SI-T3 gives notification priority to alarms.

The

Table 21

shows the response data when consecutive alarms or warnings occurs.

Table 21 Response Data for Consecutive Alarms and/or Warnings

Fault Type

Location

Description

Alarm

Drive alarm

Drive

Fault that causes damage to the drive or machinery

Communications alarm

SI-T3

Interference related to MECHATROLINK-II communications

Warning

Drive warning

Drive

Illegal operation or minor fault not posing any immediate danger

Communications warning

SI-T3

MECHATROLINK-II communications fault warning

Fault Type

<1> Refer to

Drive Fault Notification on page 32

for detail.

SI-T3 Processing

Direction of

Communications

Reset

MECHATROLINK Response

LED

(ERR)

Processing

ALARM

STATUS

WARNG

ALM

Drive alarm

CODE

<1>

1

No special processing

Required

Communications alarm

1

ON

Notification to drive

Required

Drive warning

1

No special processing

Required

Communications warning

1

No special processing

None

Not required

Fault Detection

MECHATROLINK-II Response Data Contents

Previous Value

Most Recent Value

Alarm

STATUS

WARNG

ALM

Alarm

Alarm

Most recent alarm code

0

1

Alarm

Warning

Most recent alarm code

1

1

Warning

Alarm

Most recent alarm code

1

1

Warning

Warning

Warning with the smaller warning code

1

0

Advertising