4 mechatrolink-ii option components, Mechatrolink-ii option, Communication connector – Yaskawa 1000 Series Drive Option - MECHATROLINK-II Technical Manual User Manual

Page 9: Mechatrolink-ii option led display, 4mechatrolink-ii option components

Advertising
background image

4 MECHATROLINK-II Option Components

YASKAWA ELECTRIC

SIEP C730600 50A YASKAWA AC Drive-Option Card MECHATROLINK-II Technical Manual

9

4

MECHATROLINK-II Option Components

‹

MECHATROLINK-II Option

Figure 1

Figure 1 Option Card

For details on the LEDs, Refer to

MECHATROLINK-II Option LED Display on page 9

.

‹

Communication connector

Table 2 Communication connector

‹

MECHATROLINK-II Option LED Display

The MECHATROLINK-II Option has four LEDs that indicate the option card or communication status.

„

Checking LED Operation

Table 3 MECHATROLINK-II Operation LED Status

A – Communication cable connector

E – LED (ERR)

B – Model number

F – LED (RUN)

C – Ground terminal

(installation hole)

G – LED (TX)
H – LED (RX)

D – Installation hole

I – Connector (CN101)

MECHATROLINK-II Connector

Pin No.

Signal Name

I/O

Function

A1

(NC)

Not used.

A2

SRD–

I/O

Send/receive data (–)

A3

SRD+

I/O

Send/receive data (+)

A4

(NC)

Not used.

Shell

SLD

Shield

B1

(NC)

Not used.

B2

SRD–

I/O

Send/receive data (–)

B3

SRD+

I/O

Send/receive data (+)

B4

(NC)

Not used.

Shell

SLD

Shield

LED

<1> For details on the communication error, refer to

Troubleshooting on page 30

.

Display

Status

Remarks

RUN

ON

Power supply on

SI-T3 has been successfully powered up

OFF

No power

• The drive has no power
• SI-T3 is not properly connected to the drive, or SI-T3 has no power
• An internal, self-diagnostic error occurred in the SI-T3

ERR

ON

Connection error

• SI-T3 is not properly connected to the drive
Communication error

<1>

Flashing

SI-T3 error

Error found during SI-T3's self-diagnostic check

OFF

Normal operation

• SI-T3 is properly connected to the drive
• Communication normal

TX

ON

Sending data

Data is being sent (LED may appear to be flashing)

OFF

Not sending data

• No data is being sent
• During reset

RX

ON

Receiving data

Data is being received (LED may appear to be flashing)

OFF

Not receiving data

• No data is being received
• During reset

Looking from the connector

Underside

SI-T3

A

B

I

D

E

C

H

G

F

A1

A2

A4

A3

B1

B2

B3

B4

CN3