YASKAWA ELECTRIC SIEP C730600 42B 1000-Series Option SI-P3 Technical Manual

6 Related Parameters

6

Related Parameters

The following parameters are used to set up the drive for operation with the option.

Confirm proper setting of all parameters in

Table 8

before starting network communications.

Table 8 Parameter Settings

No.

(Addr.

Hex)

Name

Description

Values

b1-01

(180)

<1>

<1> Set b1-02 to 3 to start and stop the drive through the PROFIBUS-DP network. Set b1-01 to 3 to control the frequency reference of the drive via

the PROFIBUS-DP network.

Frequency Reference
Selection 1

Selects the frequency reference input source
0: Operator - Digital preset speed d1-01 to d1-17
1: Terminals - Analog input terminal A1 or A2
2: MEMOBUS/Modbus communications
3: Option
4: Pulse Input (Terminal RP)

Default: 1
Range: 0 to 4
(Set to 3 for
SI-P3)

b1-02

(181)

<1>

Run Command Selection 1

Selects the run command input source
0: Digital Operator - RUN and STOP keys
1: Digital input terminals S†
2: MEMOBUS/Modbus communications
3: Option

Default: 1
Range: 0 to 3
(Set to 3 for
SI-P3)

F6-01

(3A2)

Communications Error
Operation Selection

Determines drive response when a bUS error is detected during communications
with the option
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

<2>

Default: 1
Range: 0 to 3

F6-02

(3A3)

External Fault from Comm.
Option Detection Selection

Sets the condition for external fault detection (EF0)
0: Always detected
1: Detected only during operation

Default: 0
Range: 0, 1

F6-03
(3A4)

External Fault from Comm.
Option Operation
Selection0

Determines drive response for external fault input (EF0) detection during
PROFIBUS communication
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

<2>

Default: 1
Range: 0 to 3

F6-06
(3A7)

<3>

Torque Reference/Torque
Limit Selection from
Comm. Option

0: Torque reference/torque limit via network communications are disabled.
1: Torque reference/torque limit via network communications are enabled.

<4>

Default: 0
Range: 0, 1

F6-07

(3A8)

Multi-Step Speed Enable/
Disable Selection when
NefRef/ComRef is Selected

0: Multi-step speed reference disabled (F7 functionality)
1: Multi-step speed reference allowed (V7 functionality)

Default: 0
Range: 0, 1

F6-08

(36A)

Reset Communication
Parameters

Determines which F6-†† and F7-†† parameters are reset to default values when
initializing the drive using A1-03.
0: Do not reset parameters
1: Reset parameters
Note: Setting this parameter does not affect communication-related parameters.
Setting this parameter only determines if communication-related parameters
(F6-†† and F7-††) are also reset when initializing with A1-03.

Default: 0
Range: 0, 1

F6-30

(3CB)

<5> <6>

PROFIBUS-DP Node
Address

0 to 125

Default: 0
Min: 0
Max: 125

F6-31

(3CC)

PROFIBUS-DP Clear
Mode Selection

Selects the action to take when a “Clear Mode” command is received
0: Resets to 0
1: Maintains the previous value

Default: 0
Range: 0, 1

F6-32

(3CD)

<6>

PROFIBUS-DP Data
Format Selection

0: PPO Type
1: Conventional

Default: 0
Range: 0, 1

F6-33

<6>

IND Data Size Selection

0: Word
1: Byte

Default: 0
Range: 0, 1