8 Parameter Process Data Object Formats

8

Parameter Process Data Object Formats

‹

Supported Parameter Process Data Object (PPO) Type Formats

Set drive parameter F6-32 to 0 to use PPO type formats. The PPO is defined for cyclic data transfer, allowing the master
and the slave to exchange process data (PZD) and parameters. Refer to the PROFIBUS specification for more
information on PPO types 1~5.

The option supports five possible PPO type formats:

• PPO type 1 (8 octets PKW + 4 octets PZD)
• PPO type 2 (8 octets PKW + 12 octets PZD)
• PPO type 3 (4 octets PZD)
• PPO type 4 (12 octets PZD)
• PPO type 5 (8 octets PKW + 20 octets PZD)

All PPO Types have the registers STW, ZSW, HSW, and HIW. These registers are not mapped directly to drive registers.

‹

Configuration of Registers

„

PKE

Bit

PPO Write

PPO Read

0

PNU number
(

Refer to Supported PNU on page 33

for details)

1
2
3
4
5
6
7
8
9

10
11

SPM always 0

SPM always 0

12

See Task ID

See Response ID
When Response ID is 7, see PWE error code

13
14
15

PPO TYPE 5: Octet-String 28

PPO TYPE 4: Octet-String 12

PPO TYPE 3: Octet-String 4

PPO TYPE 2: Octet-String 20

PKW: Parameter ID/value
PZD: Process Data, cyclically transferred
PKE: Parameter ID (1st and 2nd octet)
IND: Sub-index (3rd octet), 4th octet is reserved
PWE: Parameter value (5th until 8th octet)
STW: Control word
HSW: Main setpoint
ZSW: Status word
HIW: Main actual value

PPO TYPE 1: Octet-String 12

PKW

PZD

PKE

IND

PWE

PZD3 PZD4 PZD5 PZD6 PZD7 PZD8 PZD9 PZD10

PZD1

STW
ZSW

PZD2

HSW

HIW