8 Parameter Process Data Object Formats

38

YASKAWA ELECTRIC SIEP C730600 42B 1000-Series Option SI-P3 Technical Manual

Note: When PNU is set to 0 and INDEX is set to MEMOBUS/Modbus register number, parameter values can be read and written

instead of using PNU number.

Note: MEMOBUS/Modbus register C1-01 is 200Hex

When PNU is 0 and INDEX is 200H(512 dec), C1-01 setting value can be read and written instead of using PNU 31 (dec) and
INDEX 01.

„

Example: Writing to C1-01

Command setting

Response

„

Example: Reading to d1-17

Command setting

Response

0

002AH MEMOBUS/Modbus #

42

0

002BH MEMOBUS/Modbus #

43

0

002CH MEMOBUS/Modbus #

44

0

002DH MEMOBUS/Modbus #

45

0

002EH MEMOBUS/Modbus #

46

0

002FH MEMOBUS/Modbus #

47

0

0030H MEMOBUS/Modbus #

48

0

0031H MEMOBUS/Modbus #

49

0

0032H MEMOBUS/Modbus #

50

0

0033H MEMOBUS/Modbus #

51

0

0034H MEMOBUS/Modbus #

52

0

xxx

xxx

0

00FFH MEMOBUS/Modbus #

255

Data type

Settings

Description

PKE

701FH

7: Change parameter value in array (word)
1FH = 31 (C1 parameter)

IND

1

C1-01

PWE

10

Assign 10

STW

up to Master command

HSW

up to Master command

Data type

Settings

Description

PKE

401FH

4: Transfer parameter value (array word)
1FH = 31 (C1 parameter)

IND

1

C1-01

PWE

0

N/A

STW

up to drive status

HSW

up to drive status

Data type

Settings

Description

PKE

6029H

6: Request parameter value from array
29H = 41 (d1 parameter)

IND

11H

11H = 17 (d1-17)

PWE

0

N/A

STW

up to Master command

HSW

up to Master command

Data type

Settings

Description

PKE

4029H

4: Transfer parameter value (array word)
29H = 41 (d1 parameter)

IND

11H

d1-17

PWE

258H

d1-17 value

DPV0 PNU

Number

Description

INDEX