Si-p3 device data, Hsw/hiw, Task id – Yaskawa 1000 Series Drive Option - Profibus-DP Technical Manual User Manual

Page 30: Response id

Advertising
background image

8 Parameter Process Data Object Formats

30

YASKAWA ELECTRIC SIEP C730600 42B 1000-Series Option SI-P3 Technical Manual

„

HSW/HIW

„

Task ID

„

Response ID

‹

SI-P3 Device Data

Bit

PPO Write

PPO Read

0 to 15

Setting Frequency (

±10000/100%)

Output Frequency or Motor speed (with PG) (

±10000/100%)

ID

Description

0

No action

1

Request parameter value

2

Change parameter value (word)

3

Change parameter value (double word)

6

Request parameter value from array

7

Change parameter value in array (word)

8

Change parameter value in array (double word)

9

Request number of array elements

ID

Description

0

No action

1

Transfer parameter value (word)

2

Transfer parameter value (double word)

4

Transfer parameter value (array word)

5

Transfer parameter value (array double word)

6

Transfer number of array element

7

Task cannot be executed (with error number)

Parameter

Setting Value

Note

GSD_Revision 3

GSD

file revision 3.0.

Vendor_Name “YASKAWA

ELECTRIC”

Model_Name

“PROFIBUS-DP INTERFACE CARD SI-P3”

Ident_Number 0x0ACF

FMS_supp

0

PROFIBUS-FMS not supported

Protocol_Ident 0

PROFIBUS-DP

supported

Station_Type

0

DP-Slave.

Slave_Family 3
Revision

“V1.0”

Device revision 1.0

Hardware_Release

“V1.0”

Hardware revision 1.0

Software_Release

“V1.0”

Software revision 1.0

Implementation_type

“DPC31”

DP protocol

Redundancy

0

Redundancy NOT supported

Repeater_Ctrl_Sig 2

Supported, TTL level

24V_Pins

0

No external 24 Volt input

Set_Slave_Add_supp = 1

1

Station address is set remotely

Auto_Baud_supp

1

Automatic baud rate select

9.6_supp

1

9600 Baud

19.2_supp

1

19.2 kBaud

45.45_supp

1

45.45 kBaud

93.75_supp

1

93.75 kBaud

187.5_supp

1

187.5 kBaud

500_supp

1

500 kBaud

1.5M_supp

1

1.5 MBaud

3M_supp

1

3 MBaud

6M_supp

1

6 MBaud

12M_supp

1

12 MBaud

Advertising